P14=MAINS WAITING TIMER: This is the time between the mains voltages
entered within the limits and the generator contactor is deactivated.
P15=COOLING TIMER: This is the period that the generator runs for cooling
purpose after the load is transferred to mains.
P16=MAINS CONTACTOR TIMER: This is the period after the generator
contactor has been deactivated and before the mains contactor has been
activated.
P17=GENERATOR CONTACTOR TIMER: This is the period after the
generator phases are within the limits and before the generator contactor has
been activated.
P18=RELAY CONFIGURATION: FUEL and AUXILIARY relay configuration:
P18 VAL
AUX RELAY FUNCTION
00
Alarm
01
Fuel (Activate to Stop)
02
Preheat
03
Choke
04
Alarm
05
Fuel (Activate to Stop)
06
Preheat
07
Choke
P19 = MAINTENANCE PERIOD (ENGINE HOURS): This is the engine
periodic mainteance life as engine-hours
P20 = MAINTENANCE PERIOD (DURATION): This periodic maintenance
limit (as months) must be observed even if the engine hours limit is not
exceeded.
FUEL RELAY FUNCTION
Activate before Start
Activate before Start
Activate before Start
Activate before Start
Activate to Stop
Activate to Stop
Activate to Stop
Activate to Stop