Datakom DKM-401 Kurulum - Sayfa 2
Multimetre Datakom DKM-401 için çevrimiçi göz atın veya pdf Kurulum indirin. Datakom DKM-401 4 sayfaları.
ELECTRICAL INSTALLATION
Do not install the unit close
to high electromagnetic
noise emitting devices like
contactors, high current
busbars, switchmode power
supplies and the like.
Although the unit is protected against
electromagnetic disturbance, excessive disturbance
can affect the operation, measurement precision and
data communication quality.
Use cables of appropriate temperature range.
Use adequate cable section, at least 0.75mm
(AWG18).
For current transformer inputs, use at least
2
1.5mm
section (AWG15) cable.
The current transformer cable length should
not exceed 1.5 meters. If longer cable is used,
increase the cable section proportionally.
Current transformers must have 5A output.
Current Transformers must be
used for current measurement.
No direct connection allowed
Power Supply Input:
170 - 275VAC, 45 – 66 Hz
Different AC supply voltages available.
Measurement Input Range:
Voltage inputs:
10 - 300 V AC (L-N)
20 - 520 V AC (L-L)
Current inputs: 0.2 – 5.5 A AC
Frequency:
Accuracy:
Voltage:
Current:
Frequency:
Measurement Range:
CT range:
Power Consumption:
Voltage burden:
Current burden:
TECHNICAL SPECIFICATIONS
30 - 100 Hz
0.5%+1digit
0.5%+1 digit
0.5%+1 digit
5/5A to 5000/5A
< 4 W
< 0.1VA per phase
< 1VA per phase
PANEL CUTOUT
REQUIRED PANEL DEPTH
2
Operating Temperature:
-20°C to +80°C (-4 to +176 F).
Maximum humidity:
95% non-condensing.
Degree of Protection:
IP 54 (Front Panel) ,
IP 30 (Back panel)
Enclosure:
Non-flammable, ROHS compliant,
ABS/PC (UL94-V0)
Installation:
Flush mounting with rear retaining
brackets
Dimensions:
102x102x53mm (WxHxD)
Panel Cutout: 92x92mm
Weight:
200 gr