elsner elektronik 20559 Hızlı Başlangıç Kılavuzu

Aksesuarlar elsner elektronik 20559 için çevrimiçi göz atın veya pdf Hızlı Başlangıç Kılavuzu indirin. elsner elektronik 20559 2 sayfaları. Indoor sensor

elsner elektronik 20559 Hızlı Başlangıç Kılavuzu
EN
WG AQS/TH gl
Indoor Sensor
Technical specifications and installation instructions
Item number 20559
1.
Description
The Indoor Sensor WG AQS/TH gl transfers temperature, humidity and CO
tent of the air to the control system via radio. Several separate WG AQS/TH gl can
be taught to one control system. The teaching is described in the chapter "Learn wi-
reless connections" (manual of the control system).
The WG AQS/TH gl consists of the housing, the base plate and a frame. As an al-
ternative to the supplied frame, a frame of the switch series used in the building may
be used. You will additionally require a junction box according to DIN 49073 (not in-
cluded in scope of delivery).
For power supply (11...28 V DC), e. g. 12 V DC can be tapped from the connection
board of the control unit (multifunctional input).
Functions:
Measurement of temperature, air humidity (relative) and CO
the air
Suitable for: WS1 Color/Style, (KNX) WS1000 Color/Style/Connect, Solexa II
(Temperature evaluation only)
1.1. Scope of delivery
Housing
Base plate
Frame
You will need in addition (not supplied):
Device socket according to DIN 49073
1.2. Technical specifications
Housing
Real glass, plastic
Colours
White, glossy (similar to RAL 9010 pure
white)
Mounting
on device socket according to DIN 49073
Protection category
IP 20
Dimensions
Housing approx. 55 x 55 (W x H, mm),
mounting depth approx. 8 mm,
base plate approx. 71 x 71 (W x H, mm)
Total weight
approx. 50 g
Ambient temperature
Operating -20...+70°C, Storage -55...+90°C
Ambient air humidity
max. 95% RH, avoid bedewing
Operating voltage
11...28 V DC
Current
max. 120 mA
Data output
Wireless
Wireless frequency
868.2 MHz
Protocol
Proprietary protocol (Elsner RF)
Temperature measure-
-20...+70°C
ment range
Temperature resolution
0.1°C
Humidity measurement
0% RH ...95% RH
range
Humidity resolution
0.1%
Humidity drift
± 0.5% R.H. per year in normal air
CO
measurement
0...2000 ppm
2
range
CO
resolution
1 ppm
2
The product conforms with the provisions of EU guidelines.
1.2.1. Measurement accuracy
Deviations in measured values due to interfering sources (see chapter installation
site) must be corrected in the controller menu in order to achieve the specified sen-
sor accuracy.
To ensure a correct CO
measurement, the device must be installed in a windproof
2
socket. After applying the operating voltage, it can take up to 15 minutes until the
CO
measured value is output correctly.
2
Indoor Sensor WG AQS/TH gl • Version: 25.11.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Indoor Sensor WG AQS/TH gl
The measured temperature and humidity values can be corrected in the cont-
roller menu. This may be necessary if the values at the sensor do not correspond to
the room average (for example, if the sensor is positioned in a location which is war-
mer than average). Please be aware that usable measured values can only be achie-
ved approx. two hours after putting the sensor into operation (warm-up phase).
 Radio connections > Status (In the controller manual)
 System > Installation > Radio connection > Status > [Device]
2.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating inst-
ructions. Improper use, modifications to the device or failure to observe the opera-
con-
ting instructions will invalidate any warranty or guarantee claims.
2
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.1. Installation position
The Indoor Sensor WG AQS/TH gl is installed on a device socket.
content of
2
When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interfe-
rence include:
Direct sunlight
Drafts from windows and doors
Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
Waste heat from the control unit (when mounted above the display)
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
Connection lines and ducts which lead from warmer or colder areas to the
sensor
Temperature deviations caused by such sources of interference must be corrected
in the control system menu, in order to achieve the specified sensor accuracy (see
manual chapter Wireless connections > Status).
For a correct CO
junction box.
2.2. Composition
2.2.1. Housing
1
Fig. 2
1 Base plate
2 Openings for air circulation
3 Connection for power supply 11...28 V DC (polarity independent)
4 Catches
5 Programming LED (recessed)
6 Programming button (recessed) for teaching device
Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
Fig. 1: Sectional drawing.
The Indoor Sensor WG AQS/TH gl fits into a
standard socket (Ø 60 mm, depth 42 mm).
Installation depth
27 mm
Mounting depth
8 mm
May be installed and operated in dry interior rooms only.
Avoid condensation.
measurement it is necessary to install the device in a windproof
2
2
1
3
4
6
5