The device can enter Basic Configuration during Normal Operation. As soon as CONFIRM action
after configuration is executed the device automatically restarts in Normal Operation with the
new configuration. Particular attention has to be taken during the basic configuration manage-
CAUTION
ment and use.
Muting time-out "∞" does not comply with the requirements of IEC 61496-1. Therefore, all
possible risks must be considered and related precautions undertaken before selecting the
"∞" option.
CAUTION
A. Keep CONFIRM button pressed to enter Basic Configuration Mode.
B. A Test Pattern is shown on led interface, carefully check that all LEDs are lit in sequence from 1 to 8,
then current configuration is shown.
C. Choose function to set by SELECT button, selected led blinks.
D. Configure selected function with ENABLE button (switch led on/off).
E. Repeat B-C steps until desired configuration is visualized.
F. Keep CONFIRM button pressed to authorize the new configuration
SG4N model provides Muting and Override functions along with Automatic/Manual Restart and Exter-
nal Device Monitoring.
RX FUNCTION LIST IN MUTING (DEFAULT) OPERATION MODE (LED 3 ON YELLOW)
FUNCTION
LED #
Partial Muting
Muting Exit Delay
EDM
Restart Mode
Muting Direction
Muting Timeout
Muting Filter
BASIC CONFIGURATION MODE
SETTING
(default in bold)
Zone (A)
2
Zone (A+B)
Zone (A+B+C)
ON
3
OFF
Enabled
4
Disabled
Auto
5
Manual
T (bidirectional)
6
L (monodirectional)
10 min
7
Inf.
ON
8
OFF
LED STATUS
ESPE ZONES
4