An approved isolating valve, non-return valve, line strainer (optional but recommended)
and union must be fitted between the supply main and the RP¾/20 socket in the water
heater. All fittings must be approved by the relevant Authority. See Figure 2 for details.
Note for S.A. and W.A.: It is a state requirement that a pressure relief valve be fitted on
the cold water supply line between the non-return valve and the water heater (see Figure
2).
Warning: A separate drain line must be used for this relief valve. It is not permitted to
couple drain lines from relief valves into a single common drain line.
A relief valve is supplied with a ¾" reducing bush to fit into the RP¾/20 tank socket. The
hot water drain pipe and relief drain line to be installed as per figure 2. For the most
economical operation of the water heater, it is recommended that all hot water lines are
insulated.
PRESSURE & TEMPERATURE RELIEF VALVE
The pressure & temperature Relief Valve (rated at 1400kPa) is supplied loose with the
water heater. The valve must be installed into the top socket marked "RELIEF VALVE".
Figure 1: Clearances Required for Outdoor Installation
COLD WATER CONNECTION
HOT WATER CONNECTION