DUYAR DISEL Kurulum, Bakım ve Kullanım Kılavuzu - Sayfa 8

Kontrol Paneli DUYAR DISEL için çevrimiçi göz atın veya pdf Kurulum, Bakım ve Kullanım Kılavuzu indirin. DUYAR DISEL 11 sayfaları. Fire panel

DUYAR DISEL Kurulum, Bakım ve Kullanım Kılavuzu
DISEL
FIRE PANEL
T
Set Value = 08.0
Hys Value= 00.5
Max Value= 16
Set Value: Diesel engine stop set pressure value.
Hys
Value:
Pressure
Closed
example, if our set pressure is 8.0 bar hysteresis 1.0,
T
then the system starts to operate at 7.0 bar.
Max Value: Pressure transmitter maximum (label)
value 16 bar Set sensor value 16 bar.
Set Value = 08.0
Note: If the transmitter option is selected as active,
Hys Value= 00.5
pressure switch connection is not required.
Max Value= 16
Closed
Temp. Sensor
Closed: Closed type pressure switch usage selection.
RPM Sensor
Open: Open type pressure switch usage selection.
Fuel Sensor
Input Set
Date
: 25/04/22
Hour : 15:32
Date and time setting menu. Date and time can be
Modbus RTU
set with the up and down arrow keys and saved by
pressing the
key.
ID No
: 001
Baud Rate : 9600
6
6. SETTINGS MENU
Press the
hysteresis
adjustment.
Open
Open
Mon
INSTALLATION, MAINTENANCE and OPERATION GUIDE
button to enter the menu.
Temp. Sensor
RPM Sensor
Fuel Sensor
Input Set
Oil Sensor: Diesel oil sensor active and passive select. If
active is selected, maximum oil pressure protection is set.
For
Date
Temp. Sensor: Diesel temperature sensor active and
passive select. If active is selected maximum temperature
Hour : 15:32
protection is set.
RPM Sensor: Diesel rpm sensor active and passive select.
Temp. Sensor
If active is selected maximum and minimum rprm
RPM Sensor
protection is set.
Modbus RTU
Fuel Sensor
Fuel Sensor: Diesel fuel sensor active and passive select.
Input Set
ID No
If active is selected, fuel status can be monitored on the
screen.
Baud Rate : 9600
Input Set: Is the panel input protection setting. floater
Date
etc. Protection is done with an extra input.
Hour : 15:32
Modbus RTU
ID No
Baud Rate : 9600
ID No : It is the number of the device in the communication
system.
Baud Rate : Communication speed setting.
Parity: Number of stop bits.
: 25/04/22
Mon
: 001
: 25/04/22
Mon
: 001