d. Wire the light sensor to terminal blocks J2, +5V, and CG (Figure 19) as indicated in
21.
F
Neatly group cables/wires connecting the new control panel assembly and the old control panel.
Cover grouped cables/wires with the included protective spiral wrap as shown. Using existing
clip(s) or supplied adhesive wire guides, ensure the cable/wire bundle is secured near the hinge of
the control panel door and not hanging loosely in the control panel. All wiring should now be
complete.
Spiral wrapped wires
F
Important
CONVIRON
schematic 228124.
TB5
J2
J2
J2
B2
J24
+5V
+5V
+5V
TB5
CG
22.
Using a continuity tester or multimeter, run a continuity test from the 3 terminal on
the new controller panel assembly to both neutral and ground. NO continuity
should be found.
GREEN
WHITE
CLEAR
Figure 19
Figure 20
CMP 6050 RETROFIT INSTALLATION INSTRUCTIONS
LIGHT
SENSOR
Wire clip
Use existing wire clip(s)
if present, or adhesive
wire guides included
in Retrofit Hardware
Package
May 2013 |
257775R00