COOK FCED Kurulum, Kullanım ve Bakım Kılavuzu - Sayfa 3
Fan COOK FCED için çevrimiçi göz atın veya pdf Kurulum, Kullanım ve Bakım Kılavuzu indirin. COOK FCED 9 sayfaları. Fiberglass roof exhausters
Wiring Diagrams
Single Speed, Single Phase Motor
Ground A
T-1
T-4
Ground B
When ground is required, attach to ground A or B with No. 6 thread
forming screw. To reverse, interchange T-1 and T-4.
2 Speed, 2 Winding, Single Phase Motor
Ground A
T-1
T-4
Ground B
When ground is required, attach to ground A or B with No. 6 thread
forming screw. To reverse, interchange T-1 and T-4 leads.
Single Speed, Single Phase, Dual Voltage
Ground A
L 1
Link A
T-5
Link B
Line
J-10
Low Voltage
L 2
Ground B
When ground is required, attach to ground A or B with No. 6 thread
forming screw. To reverse, interchange T-5 and J-10 leads.
Typical Damper Motor Schematic
Fan
Motor
Transformer**
Damper
Motor*
For 3 Phase, damper motor voltage should be the same between L
L
. For single phase application, disregard L
2
*Damper motors may be available in 115, 230 and 460 volt models. The
damper motor nameplate voltage should be verified prior to connection.
**A transformer may be provided in some installations to correct the
damper motor voltage to the specified voltage.
FCE/FCRU IO&M
L 1
Line
L 2
High Speed
L 1
L 2
Low Speed
Ground A
Link A & B
T-5
J-10
Ground B
L3
L2
L1
Transformer**
Second
Damper
Motor
.
3
3 Phase, 9 Lead Motor
3 Phase, 9 Lead Motor
Y-Connection
Low Voltage
208/230 Volts
4 5 6
1
2
3
9
7
8
L 1 L 2 L 3
To reverse, interchange any 2 line leads.
2 Speed, 1 Winding, 3 Phase Motor
Motor
To reverse, interchange any 2 line leads. Motors require magnetic
Line
control.
2 Speed, 2 Winding, 3 Phase
Motor
To reverse: High Speed-interchange leads T
terchange leads T
L 1
Operation
Line
Pre-Start Checks
L 2
1. Lock out all the primary and secondary power sources.
2. Inspect and tighten fasteners and setscrews, partic-
ularly fan mounting and bearing fasteners. Refer to
Torque Chart.
3. Inspect belt tension and pulley alignment. Refer to Belt
and Pulley Installation, page 5.
4. Inspect motor wiring. Refer to Wiring Installation.
5. Ensure belt touches only the pulleys.
6. Rotate the wheel to ensure it rotates freely.
7.
Ensure fan and ductwork are clean and free of debris.
8. Close and secure all access doors.
9. Restore power to fan.
Start-Up
Turn on the fan. In variable speed units, set the fan to its
lowest speed. Inspect for the following:
• Direction of rotation
• Excessive vibration
• Unusual noise
• Bearing noise
• Improper belt alignment or tension (listen for squealing)
• Improper motor amperage or voltage
and
If a problem is discovered, immediately shut the
1
fan off. Lock out all electrical power and check for
the cause of the trouble. Refer to Troubleshooting
on page 7.
3
3 Phase, 9 Lead Motor
Delta-Connection
High Voltage
Low Voltage
460 Volts
208/230 Volts
4 5 6
8
7
6
4
7 8 9
1
2
1 2
3
L 1
L 2
L 1 L 2 L 3
High Speed
Low Speed
1
Together
2
3
Motor
L 1
4
L 2
5
Line
6
L 3
Low Speed
T
3
Low Speed
T
2
Low Speed
T
1
High Speed
T
11
High Speed
T
12
High Speed
T
13
and T
11
and T
. Both Speeds-interchange any 2 line leads.
1
2
High Voltage
460 Volts
9
7 8 9
5
3
4 5 6
1 2
3
L 3
L 1
L 2
L 3
L 1
1
L 2
2
Line
3
L 3
4
Open
5
6
L
1
L
Line
2
L
3
. Low Speed-in-
12
B51150-003