Datexel DAT1112 Hızlı Başlangıç - Sayfa 2

Verici Datexel DAT1112 için çevrimiçi göz atın veya pdf Hızlı Başlangıç indirin. Datexel DAT1112 4 sayfaları. Programmable range transmitter for thermocouple

WORKING DIAGRAM

2
- TC
MAIN
+ TC
1
AMP.
COLD
JUNCT.
COMP.
The transmitter must be powered with a voltage ranging from 12 to 32 V, applied between the -V and +V terminals.The
permissible Rload resistance, equivalent to that of the instruments applied in series to the voltage generator, must be
determined as a function of the power supply voltage value and according to the load characteristic so that its value is covered
by the working area. DAT 1112 is available in 6 different versions, covering all common sensors types. For most used sensors
a single unit cover 2 sensors, allowing substantial reduction of stocks.For programming the device, see the technical sheet
" DAT 1112 Programming Instruction ". Once the device is programmed, the calibration is carried out by adjusting the zero
and the span potentiometer as follows: apply a signal corresponding to desired minimum input signal and than adjust the
zero potentiometer to get Iout = 4,00 mA. Apply a signal corresponding to desired maximum input signal and than adjust the
span potentiometer to get Iout = 20,00 mA. Repeat these operations until the needed accuracy is obtained.
WIRING DIAGRAM
1
2
3
+
TC
DIMENSIONS
(measures in mm.)
ZERO
ON
1
7
33
43
LINEARIZER
TWO WIRE
TRANSMITTER
INTERNAL
REFERENCE
GENERATOR

OPERATING INSTRUCTIONS

-V
+V
RLoad
SPAN
8
17

LOAD CHARACTERISTICS

5
-V
4
+V
VERSION TABLE
Version
Sensor
1
K & J
2
R & S
3
T
B
4
N
5
E
6
Programmable Span
100 - 1400°C / 200 - 2500°F (K)
100 - 950°C / 200 - 1800°F (J)
650 - 1760°C / 1200 - 3200°F (R)
700 - 1760°C / 1290 - 3200°F (S)
100 - 350°C / 200 - 600°F
900 - 1820°C / 1600 - 3250°F
150 - 1350°C / 250 - 2400°F
50 - 1050°C / 100 - 1900°F
HOW TO ORDER:
DAT 1112 - 1
Version