Cookson FDO-A10 Kullanıcı El Kitabı - Sayfa 4
Kapı açma sistemi Cookson FDO-A10 için çevrimiçi göz atın veya pdf Kullanıcı El Kitabı indirin. Cookson FDO-A10 15 sayfaları. Industrial duty fire door operator
Before your operator is installed, be sure the door has been properly aligned and is working
smoothly. Refer to the Door Installation Instructions for proper operator installation. This
motor operator is an integral part of the door system. The motor operator and governor (if
provided) controls door descent speed under power outage conditions.
THE FIREDOOR CONTROLLER WILL NOT CLOSE A BALANCED DOOR IN THE ABSENCE OF AC
POWER. THE DOOR SYSTEM MUST BE ABLE TO GENERATE A MINIMUM BACKDRIVING TORQUE
OF 50 IN/LBS. AT THE OPERATOR OUTPUT SHAFT. STICKING OR BINDING DOORS MUST BE
REPAIRED. DOORS, DOOR SPRINGS, BRACKETS AND THEIR HARDWARE MAY BE UNDER
EXTREME TENSION AND CAUSE SERIOUS PERSONAL INJURY. CALL A PROFESSIONAL DOOR
SERVICEMAN TO MOVE OR ADJUST DOOR SPRINGS OR HARDWARE.
WALL MOUNTED CONTROLLER MOUNTING
1) Find a convenient location within 25' of door to mount controller.
2) Mount controller with (4) provided fasteners.
WALL MOUNTED CONTROLLER WIRING
DO NOT CONNECT POWER TO CONTROLLER AT THIS TIME
OPERATOR AND CONTROLLER MUST BE WIRED IN ACCORDANCE WITH LOCAL
ELECTRICAL CODES.
1) Wire controller to motor limit switch enclosure per wiring diagram. Use 16 GA copper
conductors.
1) Alarm inputs (Terminal A1 & A2) are used for electronic alarm devices such as smoke detectors
or similar alarm systems. The alarm activation circuit must be normally closed (NC) and must
open in an alarm condition.
DURING INITIAL SETUP MAKE SURE A CLOSED CIRCUIT IS CONNECTED TO ALARM
INPUT. FAILURE TO DO SO MAY CAUSE THE OPERATOR TO ACTIVATE SUDDENLY
WITHOUT WARNING.
AN ALARM DEVICE MUST BE CONNECTED TO THE ALARM INPUT BEFORE
INSTALLATION IS COMPLETE.
OPERATOR MOUNTING
WARNING
ALARM INPUTS
4