WARNING
5. ELECTRICAL CONNECTIONS
Installation of all wiring and connections shall be performed in accordance with, but not limited to,
the latest NFPA, U.L. and N.E.C. standards. In addition, all installations subject to Canadian
standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to
wiring material, wiring gauge related to power capacity requirements and circuit length and wiring
methods.
6. Verify voltage rating of release device to power source being utilized.
7. Connect fusible link and fire door system to release box.
8. Connect power and alarm connection to the unit.
9. Remove the "Set-Tie" cable after power and alarm connection.
"Set-Tie" cable mechanically secures release latch and must be removed to allow
proper emergency operation of release device after installation is completed.
NOTE: A trouble sounder will be activated if power is present, the latch is engaged, but the "Set-Tie"
has not been removed and/or the lever is in the "DIS-ARMED" position.
Disconnect power supply before servicing.