POWER AND GROUNDING OF ALL RACKS
When using PDUs, each PDU should be connected to a committed
branch circuit that is rated for the continuous load of all the equipment
connected. When not using a PDU, each piece of equipment should be
connected to a dedicated branch circuit.
PROTECTIVE EARTHING/GROUNDING
A main protective earthing lug is provided.
WARNING: To avoid injury to persons or loss of life,
ground rack individually to the dedicated branch circuit
earthing ground.
CONNECTING MAIN PROTECTIVE EARTHING LUG TO THE
DEDICATED BRANCH CIRCUIT EARTHING GROUND CONDUCTOR
Connect the dedicated branch circuit earthing ground conductor to
the main protective earthing stud located on the support frame using a
listed ring or closed-loop terminal.
Although equipment may physically fit into a Great Lakes rack, with
or without brackets, customers must also review and comply with the
equipment manufacturer's installation and other requirements. For
more information, please contact your Great Lakes representative or
call 1.866.879.4522
When any equipment or accessory is installed in a Great Lakes
product, the installation procedures, recommendations and product
warranty requirements of the equipment manufacturer must be
followed. Great Lakes will not be responsible for any losses or claims
arising from a customer's installation of electrical, electronic or other
third party products in any Great Lakes racks, unless caused solely by
a written configuration prepared by Great Lakes for that customer or
by a configuration provided by Great Lakes' website, any configuration
relies on complete and accurate information from the customer.
Product specifications are subject to change without prior notice.