Great Lakes Air Products EDR-A1 series Kullanım Kılavuzu - Sayfa 6

Nem Alıcı Great Lakes Air Products EDR-A1 series için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Great Lakes Air Products EDR-A1 series 8 sayfaları. Compressed air dryer. refrigeration type high inlet temperature

TROUBLESHOOTING

Sec Symptom
A
Water downstream of
dryer.
B
Drain system failure
with no condensate
discharge on test
initiation or continuous
air discharge.
C
High pressure drop
across dryer
E
E1 Power on indicator
does not illuminate
E2 Refrigeration
compressor cycles on
and off
Possible Cause(s)
1. Residual free moisture
remaining in downstream
piping
2.
Air By-pass system is open
3. Ambient temperature
surrounding downstream
piping is below the dryer's
dew point.
4. Free water (liquid) is entering
the dryer
5. Condensate is not being
drained
6. Dryer is overloaded resulting
in high dew point
7. Refrigeration system is not
functioning.
8. Suction pressure not in
operating range
9. Precooler Fan not functioning
or cooler is clogged
1. Drain strainer is clogged
2. Solenoid valve or electronic
timer failure
3. Solenoid valve diaphragm
rupture or orifice path blocked
open
4. Precooler float drain failure
1. Inlet flow exceeds
maximum capacity
2. Freezing of moisture in
evaporator is restricting inlet
air flow
Refrigeration System Fault
1. Power failure, Line fuses
blown, or disconnect open.
2. Power switch failure
1. Ambient Conditions are
above or below minimum or
maximum ranges.
1. Condenser fan failure
3. Compressor thermal
overload failure
3. Air-Cooled Units,
Dirty condenser
4. Water-Cooled Units,
High fluid temperature or low
fluid flow.
Page 6
Corrective Action
Drain low spots in system and purge with
dry air
Verify valve positions and correct valve
positions
Insulate and/or heat trace piping exposed
to low ambient temperatures or dry air to a
lower dew point.
Dryers are designed to handle saturated
air not condensed liquid. Install a separator
and coalescing filter upstream of dryer.
See section B
See capacity charts to determine correct
load
See section E
Contact your local distributor to perform
adjustments.
Clean cooler coils and/or replace fan motor
Depressurize dryer and replace or clean
drain strainer.
Replace drain solenoid and or timer
assembly
Clean or replace internal diaphragm
assembly. Clean or replace auto float
drain.
Replace float drain.
Check inlet flow vs. rated capacity
If refrigerant suction pressure is out of
standard operating range, contact your
local distributor to perform adjustments.
Have an electrician check electrical feed
and connection integrity.
Replace switch
Verify range and rectify ambient
conditions.
Replace condenser fan
Replace thermal overload and
investigate cause of failure.
Clean condenser as per required
maintenance.
Check fluid temperature, bring in range
and check for free fluid flow through
condenser. If problem persists contact
your local distributor to perform
adjustments.