ADELSYSTEM CBI-1280 Series Manuel - Sayfa 2

Güç Kaynağı ADELSYSTEM CBI-1280 Series için çevrimiçi göz atın veya pdf Manuel indirin. ADELSYSTEM CBI-1280 Series 11 sayfaları. All in one dc ups power solutions

Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy
Tel. +39 0522 345518 – Fax +39 0522 345551 – mail: [email protected]
www.adelsystem.com
All In One: U
ninterruptible
Thank you for having chosen one of our products for your work.
We are certain that it will give the utmost satisfaction and be a notable help on the job.
batteries recovery and real time diagnostic during installation and operation. The Real Time Auto-diagnostic system,
monitoring battery faults such as, battery Sulfated, elements in short circuit, accidental reverse polarity connection,
disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis Led;
during the installation and after sell. The continuous monitoring of battery efficiency, reduces battery damage risk
and allows a safe operation in permanent connection. Each device is suited for all battery types, by means of
jumpers it is possible setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel and Ni-Cd. They are
programmed for two charging levels, boost and charge, but they can be changed to single charging level by the user.
A rugged casing with bracket for DIN rail mounting provide IP20 protection degree. They are extremely compact and
cost-effective.
Safety and warning notes
WARNING – Explosion Hazard Do not disconnect Equipment unless power has been switched off or the area is known
to be non-hazardous.
WARNING – Explosion Hazard. Substitution of components may impair suitability for class I, Division 2.
WARNING – Switch off the system before connecting the module. Never work on the machine when it is
live. The device must be installed in according with UL508. The device must have a suitable isolating facility
outside the power supply unit, via which can be switched to idle. Danger of fatal Injury!
Connection (terminal and wiring):
Cable Connection: The following cable cross-sections may be used:
Solid
Stranded
2
(mm
)
(mm
In: 4.0
6.0
Out: 4.0
6.0
Signal: 0.2 – 2.5 0.2 – 2.5
The connection is made by the screw type 2.5 mm
designed for operating temperatures of > 75 °C. Wiring terminal shall be marked to indicate the proper connection for
the power supply.
P
S
Output Vdc
ower
upply
General Description
Thanks to the All In One units (DC-UPS), it will be possible to optimize power
management. The available power is automatically allocated between load and battery,
supplying power to the load is the first priority of the unit thus it is not necessary to double
the power, because also the power going to the battery will go to the load if the load so
requires. The maximum available current on the load output is 2 times the value of the
device rated current In. We call "Battery Care" the concept base on algorithms that
implement rapid and automatic charging, battery charge optimization during time, flat
AWG
Torque (Nm)
2
)
30 – 10 0.8 – 1.0 Nm
30 – 10 0.8 – 1.0 Nm
24 – 14 0.5 – 0.6 Nm
Instruction Manual CBI2801224A rev5.doc
Main Characteristics
Input: Single-phase
Output Load: power supply:
Output Battery: charging
Modbus Connection
Suited for the following battery types: Open Lead Acid,
VRLA (AFM), Gel, and Ni-Cd.
Automatic diagnostic of battery status. Charging curve
IUoUO, constant voltage and constant current Battery Life
Test function (Battery Care)
Switching technology
Four charging levels: Boost, Absorption, Trickle and
Recovery
Protected against short circuit, Over Load and inverted
polarity
Signal output (contact free) for discharged or damaged
battery
Signal output (contact free) for mains or Back-UP
Protection degree IP20 - DIN rail; Space saving
Stripping
1 Phase L N PE
Length
Input AC
7 mm
7 mm
7 mm
2
2
or 4.0 mm
terminal blocks. Use only copper cables that are
115 – 230 – 277 Vac
24Vdc; 10 A
12Vdc; 15 A
24Vdc; 10 A
12Vdc; 15 A
1 Phase L N PE
Input AC