Flexible aluminium pipes, corrosion-protected
sheet metal pipes and
material conforms to fire B1 in accordance with
DIN 4102 can be used. Exhaust air pipes should
have a nominal diameter of 150 mm.
Pay particular attention to ensuring
– the exhaust air ducts and pipes are kept as short
as possible
– the pipes are not laid at an acute angle, but as
bends and that they are inserted into the shaft at
an inclined upward angle and
– there are no cross-sectional constrictions in the
upward direction (this reduces the volume flow).
As
standard, the blow-out opening of the wall hood
is in the upward direction.
To pass exhaust air through the outer wall, we
recommend the use of our telescopic wall box
TM 150-045 (Ø 150).
Note:
To prevent the ingress of water, e.g. condensate or
rain water from an uncovered exhaust air shaft, our
condensate separator RV 060-150 must be installed
in the exhaust air line. The condensate separator
must still be acciessible after installation.
The duct units listed below are available
depending on the height of the ceiling:
Installation accessories for exhaust air mode
Stainless steel-design ventilation duct:
LK 010-012 for ceiling heights of
LK 010-022 for ceiling heights of
Aluminium-design ventilation duct:
LK
011-012
for ceiling heights of
LK
011-022
for ceiling heights of
exhaust air pipes whose
that
2.25 - 2.64 m
2.64 - 3.02 m
2.25 - 2.64 m
2.64 - 3.02 m
Installation accessories for circulating air mode
Stainless steel-design ventilation duct:
LK
010-112
for ceiling heights of
LK 010-122 for ceiling heights of
Aluminium-design ventilation duct:
LK
011-112
for ceiling heights of
LK
011-122
for ceiling heights of
The dimensions above refer to a distance of 1.60 m
from the floor to the bottom edge of the hood.
If required, custom made duct units are available at
an extra charge.
The socket must be place behind the duct cover on
the wall.
260
550
Fig. 18
2.36 - 2.64 m
2.64 - 3.02 m
2.36 - 2.64 m
2.64 - 3.02 m