Automated Logic M4106nx Teknik Talimatlar - Sayfa 6

Kontrolör Automated Logic M4106nx için çevrimiçi göz atın veya pdf Teknik Talimatlar indirin. Automated Logic M4106nx 10 sayfaları.

the total current of all "B" terminals
must not exceed 200mA. If the voltage
measured from the "B" terminal to Gnd
is less than 18VDC, you need to use an
additional external power supply.
• Dry Contact: A 5VDC wetting voltage is
used to detect contact position. This
results in a 0.5mA maximum sense
current when the contacts are closed.
Table 2. Input wiring restrictions
Maximum
Input
Length
0 to 5VDC
50 feet
15 meters
Thermistor
50 feet
Dry contact
15 meters
0 to 20mA
150 feet
46 meters
The M4106nx accumulates up to ten input
pulses per second.
1. Be sure the M4106nx's power is off before
wiring any inputs or outputs.
2. Connect the input wiring to the screw
terminals on the module as shown in
Figure 7.
NOTE If a 4-20 mA sensor uses an
external 24VAC power supply, connect
one leg of the 24VAC supply to the module
ground.
3. Set the configuration jumper for each
input to indicate the type of input
used.Make sure the jumper is positioned
correctly, and be sure to grip the jumper
by the sides only. See Figure 8.
4. For each input, enter the channel number,
offset, and gain on the Function Block's
Parameter page in SuperVision. Valid
Revised 3/29/00 • M4106nx
Minimum
Gauge
Shielding
24AWG
shielded and
grounded to
"
"
module's
B
or Gnd
terminal
24AWG
shielded and
grounded to
"
"
module's
B
or Gnd
terminal
20AWG
unshielded
P W R
0 -5 V D C
O U T
G N D
D R Y
C O N T A C T
P A S S IV E
T R A N S D U C E R
4 -2 0 m A
1 2 V o r 2 4 V
L O O P IN P U T
T H E R M IS T O R
O U T
3 W IR E
P W R
4 -2 0 m A
G N D
O U T +
4 W IR E
O U T -
4 -2 0 m A
G N D
P W R
IS O L AT E D AC
O U T +
o r D C PO W ER
O U T -
S U PP L Y
Figure 7. Input Wiring
channel numbers are listed in "Channel
Numbers" on page 8.
5. To verify each input's operation, have
each sensor create a known value and
compare it to the condition reported on
the FB's Status page.
U niversal In put
M o d e Select
Figure 8. Jumper Position
6
© 2000 Automated Logic Corporation
U n iv e rsa l In p u t
M o d e S e le ct
In p u ts
5 V M a x , 2 0 m A M a x
T O M O D U L E G N D
Grip
Her e