DynaGen AST3225 Kurulum ve Kullanım Kılavuzu - Sayfa 5
Anahtar DynaGen AST3225 için çevrimiçi göz atın veya pdf Kurulum ve Kullanım Kılavuzu indirin. DynaGen AST3225 19 sayfaları. Automatic transfer switch
5
1:2 Relay Board Module:
The relay board provides means for automatic transfer of a utility source of power to an
emergency source of power, upon loss of the utility, and switches back again, upon
restoration of the utility. The relay board has no built in delays for transfer. Any required
delays must come from an external source (ie. engine controller, timer module).
1:2:1 Sensing:
The relay board module provides 2 types of voltage sensing:
i). Relay Coil Sensing:
When the slide switch, located on the relay module, adjacent to the 8 pin octal socket, is
in the ON or UP position, utility voltage sensing is provided by means of an on board
relay coil. The relay coil characteristics set the pick up and drop out of the main utility
source.
ii). Adjustable Voltage Sensing:
When the slide switch is in the OFF, or DOWN position, the on board relay coil is
bypassed, and voltage sensing is provide by a UL approved voltage sensing module,
which plugs into the 8 pin octal socket. The adjustable voltage monitor is a single set-
point voltage monitor. Input voltages 10% below the set-point range will cause the output
contacts to de-energize (unit is adjustable from (190-240 VAC). The adjustable drop out
relay recommended for use with the AST3225 Automatic Transfer Switch is the Symcom
201-200-SP-T Rev 5.20.
ADJUSTMENT PROCEDURE
Rotate the line voltage adjustment to the nominal line voltage feeding the transfer switch.
Measure the line to line voltage. If the voltage is up to 10% below the adjustable voltage
set point, and the LED on the monitor is illuminated, the adjustable voltage monitor is
working properly. The voltage sensor can also be factory set to customer specifications.
1:2:2 System Operation:
The relay board module has provisions for 12 and 24 VDC operation. The relay board
comes factory set for 12 VDC applications. Changing from 12 to 24 VDC will require
cutting the 2 jumper wires located next to the 5-position header.
Automatic
Manual for AST3225
Transfer Switch