DayTronic M2 Kullanıcı Kılavuzu - Sayfa 7

Ölçüm Cihazları DayTronic M2 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. DayTronic M2 20 sayfaları.

4. Setting up the device

4.1. Switching-on
Once the installation is complete, you can start the device by applying the voltage supply.
Before, check once again that all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (8 8 8 8 8) is displayed
followed by an indication of the software type and, after that, also for 1 second the software
version. After the starting sequence, the device switches to operation/display mode.
4.2. Standard parameterisation: (Flat operation level)
To parameterize the display, press the [P] key in operating mode for 1 second. The display
then changes to the menu level with the first menu item TYPE.
Menu level
Selection of the device address
Device addresses from 1-125 can be parametrised. The address 126 is preset as
default value, which is the delivery state. After changing this parameter, the device
does a soft test bevor switching back into operation mode. After this, the new address
will be directly in use.
Setting the decimal point,
The decimal point on the display can be moved with [▲] [▼] and confirmed with [P].
The display then switches back to the menu level again.
Adjusting the brightness
With this parameter the brightness of the display can be reduced onto 25% of the total
brilliancy. With [P] the selection is confirmed and the device switches back into menu
level.
Parameterisation level
Adr
:
dot
:
brt
:
5
4. Setting up the device