Hickok FPT2600-EX1 Kullanıcı Kılavuzu - Sayfa 11

Test Ekipmanları Hickok FPT2600-EX1 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Hickok FPT2600-EX1 16 sayfaları. I/m handheld fuel cap test system

Procedure—Part 1
1. Set the Pass/Fail Standard swing valve to PASS (green).
2. Push the Press To Start button to turn the tester on. The LEDs will light
in the following order:
• All LEDs will light briefly.
• The green PASS LED will turn on
during the auto zero function
and then turn off.
• The red READY LED turns on
indicating the tester has auto
zeroed and is ready for testing.
3. Immediately install the Pass/Fail Standard to the tester's quick
disconnect fitting to begin the test.
4. With the Pass/Fail Standard connected to the tester and the tester
powered on (red READY LED on), begin pumping the handle to build
up pressure and start the test.
Continue pumping as the PASS LED turns on, stopping after the NO
LEAK LED turns on. The 10 second test is automatically initiated.
Note: If the OVER PRES LED turns on, stop pumping immediately and
allow test to start.
At the end of the test, the results are displayed by the tester flashing
the appropriate LED:
Test Passed—Green PASS LED flashes
Test Failed—Red FAIL LED flashes, or the standard cannot be
Procedure—Part 2
1. Follow the same instructions for part 1 except set the swing valve to
Fail (Red).
Connecting & Using the Tester
pressurized (the No Leak LED will not turn on with
continued pumping)
FPT2600-EX1 User Guide
11