HID EdgePlus Hızlı Kurulum Kılavuzu - Sayfa 3

Kart Okuyucu HID EdgePlus için çevrimiçi göz atın veya pdf Hızlı Kurulum Kılavuzu indirin. HID EdgePlus 14 sayfaları.

EdgeReader and EdgePlus Installation

Introduction

®
The HID EdgeReader™ and EdgePlus™ are a unique IP-enabled intelligent access control processor
and host interface solution in a single unit. They are designed to provide a complete and full-featured
access control hardware/software infrastructure at "the edge" of the network for OEM software host
systems.
Today, as more IT departments become involved in the security system implementation decision-
making process, they prefer that access control be managed over the network. The EdgeReader and
EdgePlus address this by offering an IP-based solution incorporating PoE capability that takes
advantage of existing LAN and CAT-5 cable infrastructure. In addition, they can be fully integrated into
any host system utilizing an IP network software interface.

Parts List

Description
EdgeReader or EdgePlus
- Mounting screws
- 2.2K EOL resistors
- Quick Installation Guide
- Quick Reference Card

Product Specifications

Description
Power Supply
Maximum current at 12VDC per EdgeReader
Average operating current at 12VDC
Maximum Supplied Power
- ERW400 EdgeReader
- E400 EdgePlus
Relay Contact Rating
Operating temperature range
Humidity

Cable Specifications

Cable Type
Input Circuits *
500 feet (150 m)
Output Circuits *
500 feet (150 m)
Wiegand
500 feet (150 m) to reader
(Remote
mounted reader
only)
Ethernet
328 feet (100 m)
Power Supply
----
+12 VDC IN
* Minimum wire gauge depends on cable length and current requirements.
April 2007
12-16VDC or Power over Ethernet (PoE)
1 Amp
300 mA – ERW400 EdgeReader and no accessories
600 mA – Split between one or two relays
700 mA – Split between a reader and one or two relays
2 Amps @ 30VDC
32°-122°F (0°-50°C)
5% to 95% non-condensing
Length
2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C
(18AWG), or equivalent.
2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG), or
equivalent.
ALPHA 1299C, 22AWG, 9-conductor, stranded, overall shield.
Fewer conductors needed if all control lines are not used.
Cat5, Cat5E, and Cat6
Refer to your Power Supply Installation Guide.
© 2007 HID Global Corporation. All rights reserved.
Quantity
1
4
8
1
1
Specification
Specification
Part No. 82000-901
Page 3 of 14