Automation Components WT2630AR/P Kurulum ve Çalıştırma Talimatları - Sayfa 2

Aksesuarlar Automation Components WT2630AR/P için çevrimiçi göz atın veya pdf Kurulum ve Çalıştırma Talimatları indirin. Automation Components WT2630AR/P 3 sayfaları. Humidity and temperature wall sensor series

Automation Components WT2630AR/P Kurulum ve Çalıştırma Talimatları
Once the sensor location has been determined mount the sub-base on an inside wall approximately 4.5
feet from the oor (or in the speci ed location) to allow exposure to the average zone temperature using
two #8 screws, Velcro™ or double sided tape.
Locate and record the sensor ID numbers located on a label inside the unit prior to mounting.
Do not mount the sensors on an outside wall, on a wall containing water pipes or near air ducts. Avoid
locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun.
Attach the wall sensor to the sub-base by tightening the two locking screws at the bottom of the sub-base.
NOTE: The locking screw must be installed for a secure installation.
counter-clockwise to secure the cover.
The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low. A
low battery signal is also sent to the receiver for remote indication that the battery should be replaced. If
the battery is not replaced in approximately 2 months the battery voltage will become so low that the Low
Battery and Data-Link LEDs will not blink. Replace the battery and the Data-Link LED will start blinking
while the sensor is re-establishing communications with the receiver.
PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.
CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE
MAY BE AFFECTED.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
The screws are turned
Version: 5.0
I0000685