Dynalite DMC810GL Kurulum Kılavuzu - Sayfa 12

Kontrolör Dynalite DMC810GL için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. Dynalite DMC810GL 12 sayfaları. Leading edge dimmer/hf ballast controller

Dynalite DMC810GL Kurulum Kılavuzu
useful DyNet op codes
.........................................................................................................................
Stop Fading
Byte 0
1C hex
Byte 1
AREA
Byte 2
CHANNEL NUMBER (0 origin)
Byte 3
76 hex
Byte 4
Unused (usually 0)
Byte 5
Unused (usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Area 4 Channel 6 Stop Fading:
[1C] [04] [05] [76] [00] [00] [FF] [66]
Report Preset (reply from dimmers -
response from 63 message)
Byte 0
1C hex
Byte 1
AREA
Byte 2
PRESET NUMBER (0 origin)
Byte 3
62 hex
Byte 4
Unused(usually 0)
Byte 5
Unused(usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Area 4 is currently in Preset 6:
[1C] [04] [05] [62] [00] [00] [FF] [7A]
Request Preset (sent to dimmers)
Byte 0
1C hex
Byte 1
AREA
Byte 2
Unused(usually 0)
Byte 3
63 hex
Byte 4
Unused(usually 0)
Byte 5
Unused(usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Request Current Preset of Area
4:
[1C] [04] [00] [63] [00] [00] [FF] [7E]
Start Fading to A Level (All Channels in an
Area)
Byte 0
1C hex
Byte 1
AREA
Byte 2
LEVEL (01 = 100%, FF = 0%)
Byte 3
79 hex
Byte 4
Fade Rate low byte (usually
100)
Byte 5
Fade Rate high byte (usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Fade Area 4 to 50% over 2 sec:
[1C] [04] [82] [79] [64] [00] [FF] [82]
Stop Fading (All Channels In An Area)
Byte 0
1C hex
Byte 1
AREA
Byte 2
Unused (usually 0)
Byte 3
7A hex
Byte 4
Unused (usually 0)
Byte 5
Unused (usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Halt the Fade in Area 4 at the
current level:
[1C] [04] [00] [7A] [00] [00] [FF] [67]
Toggle Channel State (PresetOff or
OffPreset)
Byte 0
1C hex
Byte 1
AREA
Byte 2
CHANNEL NUMBER (0 origin)
Byte 3
70 hex
Byte 4
UNUSED (usually 0)
Byte 5
UNUSED (usually 0)
Byte 6
TBAR (usually FF hex)
Byte 7
CHECKSUM
Example: Toggle Channel State of Area 4
CH8:
[1C] [07] [09] [70] [00] [00] [FF] [65]
Program Toggle Preset (sent to dimmer)
Byte 0
1C hex
Byte 1
AREA
Byte 2
Channel Number (0 origin)
Byte 3
7D hex
.........................................................................................................................
Byte 4
LEVEL
Byte 5
Unused (usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Save the Level of Area 4 CH8 to
the Toggle Preset:
[1C] [07] [09] [70] [00] [00] [FF] [65]
Leave Program Mode - Saves light level to
the current Preset (sent to dimmers)
Byte 0
1C hex
Byte 1
AREA
Byte 2
Unused (usually 0)
Byte 3
8
Byte 4
Unused (usually 0)
Byte 5
Unused (usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Save the Current Channel
Levels of Area 4 to the Current Preset:
[1C] [04] [00] [08] [00] [00] [FF] [D9]
Lock Control Panels (sent to dimmers with
Keyboard inputs and Smart Panels)
Byte 0
1C hex
Byte 1
AREA
Byte 2
Unused (usually 0)
Byte 3
15
Byte 4
Unused (usually 0)
Byte 5
Unused (usually 0)
Byte 6
Join (usually FF hex)
Byte 7
Checksum
Example: Lock All Control Panels in Area
6:
[1C] [06] [00] [15] [00] [00] [FF] [CA]
DMC810GL Instruction Manual Rev B.DOC