ANC-120e
USB to DH+ Adapter
HMI
HMI screen enables you to use an IP address to communicate to a specific DH+ node directly. The HMI
is used to enable PanelView's or other devices in an ethernet network to communicate with DH+ nodes
when they do not have the ability to use DH+ addresses. Here is an example of configuration.
For this example:
ANC-120e IP address = 192.168.137.2
*1
SLC5/04
DH+ node = 03 (in decimal, not octal)
*2
PANELVIEW PLUS 6
will use IP address = 192.168.137.229
IP address assigned to SLC5/04 = 192.168.137.230
*1 If your SLC or PLC is in node 0 please use 00 in the HMI configuration.
*2 Always assign an IP address that is not being used in the network.
1. Turn ON the first row in the ANC-100e's "HMI" tab in the web interface
2. Enter an IP address that is not being used (keep in mind that it has to be in the same network
the ANC-100e is) and enter the DH+ node of the device that you are connecting to
3. You can repeat steps 1 and 2 for each row to communicate with up to 5 DH+ devices if
necessary, using a different IP address in each row
Click "Apply" and wait for the unit to reboot (5 seconds)
2
©Automation Network Inc. 2016
1