I/O Sistemleri Automationdirect.com Productivity 2000 P2-08ADL-1 için çevrimiçi göz atın veya pdf Manuel indirin. Automationdirect.com Productivity 2000 P2-08ADL-1 8 sayfaları. Analog input
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
1200mW
Enclosure Type
Open Equipment
UL508 File E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System or removable terminal block
Field Wiring
(not included). See "Wiring Options" on page 5.
See the "EU Directive" topic in the Productivity Suite
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Terminal Type
18-position Removable Terminal Block
Weight
100g (3.5 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com
Input Specifications
Input Channels
8 sinking
Module Signal Input Range
0-20 mA
Signal Resolution
13-bit
Resolution Value of LSB
0-20 mA = 2.44μA per count
(least significant bit)
(1LSB = 1 count)
Data Range
0-8191 counts
Input Type
Single-ended (1 common)
Maximum Continuous Overload
±31mA
Input Impedance
124Ω, ±0.5%, 1/2W Current Input
Filter Characteristics
Low Pass, -3dB @ 120Hz
2ms per channel
Sample Duration Time
(does not include ladder scan time)
All Channel Update Rate
20ms
Open Circuit Detection Time
Zero reading within 100ms
Conversion Method
Successive approximation
Accuracy vs. Temperature
±75PPM / ºC maximum
0.5% of range
Maximum Inaccuracy
(including temperature drift)
±0.037% of range
Linearity Error (end to end)
Monotonic with no missing codes
Input Stability and Repeatability
±0.024% of range
Full Scale Calibration Error
±0.098% of range
(including offset)
Offset Calibration Error
±0.098% of range
Max Crosstalk
4 counts / 0.048% of range
Recommended Fuse (external)
Edison S500-32-R, 0.032A fuse
External DC Power Required
24VDC (-20% / + 25%), 30mA
Tech Support 770-844-4200