Automationdirect.com Productivity 3000 P3-08AD Hızlı Başlangıç Kılavuzu - Sayfa 2
I/O Sistemleri Automationdirect.com Productivity 3000 P3-08AD için çevrimiçi göz atın veya pdf Hızlı Başlangıç Kılavuzu indirin. Automationdirect.com Productivity 3000 P3-08AD 8 sayfaları. Analog input
General Specifications
Operating Temperature
0° to 60°C (32° to 140°F),
Storage Temperature
-20° to 70°C (-4° to 158°F)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800 VAC applied for 1 second
Insulation Resistance
>10MV @ 500 VDC
Heat Dissipation
1.1 W
Enclosure Type
Open Equipment
Agency Approvals
UL508 file E157382, Canada & USA
UL1604 file E200031, Canada & USA
CE (EN61131-2*)
This equipment is suitable for use in Class 1,
Division 2, Groups A, B, C and D or non-hazardous
locations only.
Module Keying to Backplane Electronic
Module Location
Any I/O slot in any local, expansion, or remote
base in a Productivity3000 System.
Field Wiring
Removable terminal block (not included). Use
ZIPLink Wiring System or optional terminal block.
See "Wiring Options" on page 5.
EU Directive
See the "EU Directive" topic in the
Productivity3000 Help File. Information can also be
obtained at: www.automationdirect.com/P3000
Terminal Type (not included) 20-position removable terminal block
Weight
105g (3.73 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
WARNING:
Explosion hazard – Substitution of components may impair suitability
for Class I, Division 2.
AVERTISSEMENT:
Risque d'explosion : la substitution de composants peut com-
promettre la convenance pour la Classe I, Zone 2 ou pour la Classe I, Division 2.
2
www.automationdirect.com/P3000
Input Specifications
Input Channels
8
Module Signal Input
±10VDC, ±5VDC, 0 - 5VDC, 0 - 10VDC,
Ranges
0 - 20mA
Signal Resolution
16-bit
Resolution Value of LSB
1 LSB = 1 count
(least significant bit)
±10V = 305µV
±5V = 152µV
0 - 5V = 76µV
0 - 10V = 152µV
0 - 20mA = 0.305µA
Data Range
0 to 65535 counts unipolar
-32768 to +32767 counts bipolar
Maximum Continuous
±31mA, current input
Overload
±100V, voltage input
Input Impedance
1MV ±10% voltage input
250V ±0.1%
Hardware Filter
Low pass 1st order, -3dB@48Hz
Characteristics
Sample Duration Time
455µs per channel
(does not include ladder scan time)
All Channel Update Rate
4ms
Open Circuit Detection
Zero reading within 1s (current input only)
Time
Conversion Method
Successive Approximation
Accuracy vs. Temperature ±10PPM / °C Maximum
Maximum Inaccuracy
0.1% of range voltage, 0.2% of range current (including
temperature drift)
Linearity Error (end to
±0.01% of range max., ±10V & ±5V
end)
±0.015% of range max., 0-10V, 0-5V & 0-20mA
Monotonic with no missing codes
Input Stability and
±0.035% of range (after 10 min. warmup)
Repeatability
Full Scale Calibration
±0.2% of range maximum
Error
Offset Calibration Error
± .065% of range maximum
Max Crosstalk
-96dB
Recommended Fuse
Edison S500-32-R, .032A fuse
(external)
on current inputs only
External DC Power
24VDC (-20% / + 25%) 33mA
Required
Tech Support 770-844-4200
W. current input
1/4