SENSITIVITY TEST
1. Press and hold the TEST/SILENCE button for 4 seconds. Once the test
starts, the smoke alarm LED fl ashes 1 to 9 times.
2. Count the number of LED fl ashes and use the following table to determine
if any action is necessary.
FLASHES
INDICATION
Unserviceable
0-1
hardware fault
Unit is becoming
2-3
insensitive
Unit is within normal
4-7
sensitivity range
Unit is becoming too
8-9
sensitive
After the LED fl ashes, if the sensitivity is within limits and all other tests pass,
the unit goes into alarm and resets after 7 seconds. If the sensitivity is not
within limits, or an unserviceable hardware fault has been detected, the unit
LED extinguishes until the unit is serviced.
LED FUNCTIONS
Flashing — Flashes every 9 seconds to indicate normal operation.
On — Detects smoke
Off — Trouble or maintenance is required.
WHEN TO REPLACE THE BATTERIES
When the batteries are low, the unit extinguishes its LED and chirps every 45
seconds until the batteries are replaced. The low battery trouble chirps can be
silenced for 24 hours by pressing the TEST/SILENCE button. Battery life is a
minimum of one year, and varies depending on how often the unit is tested.
REPLACING THE BATTERIES
Use only 3V lithium batteries listed on the battery compartment cover.
1. Remove the unit from the mounting base, grasp the unit and turn it
counterclockwise approximately 15 degrees.
2. Slide the battery compartment cover away from the smoke alarm to
unsnap it and lift it off. See Figure 2.
3. Remove the batteries and dispose of them properly.
4. Observing correct polarity, insert two new 3V lithium batteries into the
battery compartment and replace the cover.
5. Reattach the unit to the mounting base. See Installation , Step 6.
6. Test the system.
CLEANING
Clean the cover with a dry or damp (water) cloth as needed to keep it free
from dust and dirt.
When necessary, clean the interior and replace the optical chamber (part
number 230802) as follows:
1. To remove the unit from the mounting base, grasp the unit and turn it
counterclockwise approximately 15 degrees.
2. Remove the batteries.
3. Slide a fl at-blade screwdriver in the slot on the alarm cap and gently push
the handle down to pry the alarm cap up and off. See Figure 4.
4. Squeeze the optical chamber where indicated and pull it up and away
from the optical base and discard. See Figure 5.
5. Blow out or use a soft-bristled brush to remove all dust and dirt from the
optical base.
6. Line the new smoke chamber up with the optical base by lining up the
arrows on the optical chamber to the latches on the optical base. Ensure
that the LED cavity in the optical chamber is above the LED and snap the
optical chamber down into place.
7. To replace the alarm cap as follows:
• Line the alarm cap up with the unit.
• Insert the alarm cap into the unit and turn clockwise approximately 15
degrees. It should snap fi rmly into place.
2
ACTION
Reset and rerun sensitivity test. If
the error persists, replace the unit.
Clean and reset the unit. Rerun
sensitivity test. If the error persists,
replace the unit.
No action required
Verify that the optical chamber is
snapped down securely. Clean
the unit and replace the optical
chamber.
8. Observing proper polarity, replace the batteries and the battery
compartment cover.
9. Reattach the unit to its mounting base. See Installation , Step 6.
10. Test the unit sensitivity.
MAINTENANCE
The units are designed for easy fi eld service and maintenance. When installed
and used properly, they require minimal maintenance.
The unit should be tested weekly.
When a unit requires maintenance, it extinguishes its LED and stops sending
supervisory signals to the alarm Control Panel.
If the Control Panel indicates supervisory trouble for the smoke alarm, perform
the sensitivity test and follow the recommended actions.
SPECIFICATIONS
Voltage
Typical average standby current
Typical test current
Typical alarm current
Battery type
Low battery threshold
Sounder
Low battery beep rate
Sensitivity
Operating temperature
Operating humidity range
Color
Alarm dimensions
Base dimensions
Drift compensation adjustment
Heat detector specifications
Rate-of-rise
Fixed
Listings
Figure 4. Removing the Smoke Alarm Cap
Optical
chamber
latch
Alignment
arrows
Figure 5. Smoke Alarm Parts
3VDC
35µA
2mA
70mA
®
3V lithium, Duracell
123, Panasonic
®
CR123A, Sanyo
123A
2.70V causes low battery signal
85dBa at 10' temporal pattern
1 every 45 sec.
2.2% ± 1.3% / ft.
40°-100°F (4.4°-37.8°C)
0-95% non-condensing
White
5.6" x 2.4" (14.2 cm x 6.1cm)
5.4" x 0.46" (13.7 cm x 1.17cm)
0.5% / ft. max.
15°F/min>105°F
(8.3°C/min>40.6°C
135°F ± 5°F (57.2°C ± 2.8°C)
ETL, UL217, CSFM
Optical base
Optical
chamber
Alarm Cap
®