Cautions during Use

• Follow instructions in 'Cautions during Use' . Otherwise, it may cause unexpected
accidents.
• Check the polarity of the terminals before wiring the temperature sensor.
• For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and
length. For thermocouple (TC) temperature sensor, use the designated compensation
wire for extending wire.
• Keep away from high voltage lines or power lines to prevent inductive noise. In case
installing power line and input signal line closely, use line filter or varistor at power line
and shielded wire at input signal line. Do not use near the equipment which generates
strong magnetic force or high frequency noise.
• Install a power switch or circuit breaker in the easily accessible place for supplying or
disconnecting the power.
• Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature
controller.
• When changing the input sensor, turn off the power first before changing. After
changing the input sensor, modify the value of the corresponding parameter.
• 24 VACᜠ, 24-48 VDCᜡ power supply should be insulated and limited voltage/current
or Class 2, SELV power supply device.
• Make a required space around the unit for radiation of heat. For accurate temperature
measurement, warm up the unit over 20 min after turning on the power.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
• Do not wire to terminals which are not used.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
T
C
N
4
-
❶ Size
S: DIN W 48 × H 48 mm
M: DIN W 72 × H 72 mm
H: DIN W 48 × H 96 mm
L: DIN W 96 × H 96 mm
❷ Power supply
2: 24 VACᜠ 50/60 Hz, 24-48 VDCᜡ
4: 100-240 VACᜠ 50/60 Hz

Product Components

• Product
• Bracket

Sold Separately

• Terminal protection cover: RSA / RMA / RHA / RLA Cover
2
R
-
❸ Wiring type
No mark: Bolt
P: Connector plug connection
• Instruction manual

Specifications

Series
TCN4□-22□-□
24 VACᜠ 50/60 Hz ±10%
Power supply
24 - 48 VDCᜡ ±10%
Power consumption AC: ≤ 5 VA, DC: ≤ 3 W
Sampling period
100 ms
Input specification
Refer to 'Input Type and Using Range.
Relay
250 VACᜠ 3A, 30 VDCᜡ 3A, 1a
Control
output
SSR
12 VDCᜡ±2 V, ≤ 20 mA
Alarm output
250 VACᜠ 1 A 1a
Display type
7 Segment (red, green), LED type
Control
Heating,
ON/OFF, P, PI, PD, PID Control
type
Cooling
Hysteresis
1 to 100 (0.1 to 50.0) ℃/℉
Proportional band
0.1 to 999.9 ℃/℉
(P)
Integral time (I)
0 to 9,999 sec
Derivative time (D)
0 to 9,999 sec
Control cycle (T)
0.5 to 120.0 sec
Manual reset
0.0 to 100.0%
Mechanical ≥ 5,000,000 operations
Relay
life
OUT1/2: ≥ 200,000 operations (load resistance: 250 VACᜠ 3 A )
Electrical
cycle
AL1/2: ≥ 300,000 operations (load resistance: 250 VACᜠ 1 A )
Between input terminal and
Dielectric strength
power terminal: 1,000 VACᜠ
50/60 Hz for 1 min
0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min) in each X, Y, Z
Vibration
direction for 2 hours
Insulation
≥ 100 MΩ (500 VDCᜡ megger)
resistance
±2 kV square shaped noise (pulse width: 1 ㎲) by noise simulator
Noise immunity
R-phase, S-phase
≈ 10 years (non-volatile semiconductor memory type)
Memory retention
Ambient
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
temperature
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Mark: ▱, double or reinforced
insulation (dielectric strength
Insulation type
between the measuring input
part and the power part: 1 kV)
Approval
ᜢ ᜧ ᜫ
• TCN4S: ≈ 100 g (≈ 147 g)
Unit weight
(packaged)
• TCN4H: ≈ 124 g (≈ 194 g)
TCN4□-24□-□
100 - 240 VACᜠ 50/60 Hz ±10%
≤ 5 VA
Between input terminal and power
terminal: 2,000 VACᜠ 50/60 Hz for 1
min
Mark: ▱, double or reinforced
insulation (dielectric strength
between the measuring input part
and the power part: 2 kV)
• TCN4M: ≈ 133 g (≈ 203 g)
• TCN4L: ≈ 179 g (≈ 275 g)