Autool LM110 Kullanıcı Kılavuzu - Sayfa 6
Ölçüm Cihazları Autool LM110 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Autool LM110 12 sayfaları. Digital manifold gauge
1. Turn off the valve.
2. Press POWER Button to start the instrument. Press FUNCTION Button to select
Pressure Test Interface with Evaporation Temperature or Condensation Temperature
as below figures.
Pressure Test Interface with
Pressure Test Interface with
Evaporation Temperature
Condensation Temperature
3. There will be 10 digits displayed after instru-ment turned on. Long press ZERO
button to zero reading.
4. Long press SETTING button to enter setting mode for adjusting unit and type of
refrigerant. (see 6-4 SETTING)
5. Fill refrigerant according to instructive opera-tion of refrigeration system.
6. Obtain test readings of pressure test, running test, evaporation temperature and
condensa-tion temperature.
7. Turn off valve after filling completed. Rapidly remove connection between
instrument and refrigeration system and refrigerant source.
8. Turn off the instrument.
NOTE: Filling operation of different equipment or refrigerant may vary. Please read
carefully the relevant specific operation requirements for filling operation, so as to
avoid damage to user or equipment caused by improper operation.
6.2. Vacuum Operation
Vacuum operation tests vacuum pressure value and calculates vacuum degree.
Operation Instructions are as follows.
1.Turn off the valve.
2.Press POWER button to start the instrument. Press FUNCTION Button to select
Vacuum Test Interface as below figures.
5