AutoPulse 4100-3111 Kurulum Talimatları Kılavuzu - Sayfa 3

Kontrol Ünitesi AutoPulse 4100-3111 için çevrimiçi göz atın veya pdf Kurulum Talimatları Kılavuzu indirin. AutoPulse 4100-3111 10 sayfaları. Idnet 2 sprinkler card and idnet loop card

4100-3113AR IDNet 2 Sprinkler Card, and 4100-3111 IDNet Loop Card Installation Instructions

Setting the address

The DIP switch SW1 is used to set the sprinkler card address as defined in the Autopulse Panel Programmer job, for more information, see
Programming. From left to right, these switches are SW1-1 through SW1-8:
• SW1-1. This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU. Set this switch
to ON.
• SW1-2 through SW1-8. These switches set the card address within the sprinkler control panel. See Figure 6 for a complete list of the switch
settings for all of the possible card addresses.
You must set these switches to the address that the Autopulse Panel Programmer assigns to the card.
page 3
Figure 5: DIP Switch SW1
579-1214AR Rev. B