Product Installation Guidelines
MOUNTING DETAILS
Face plate cut out position
-
A position above and to the right of the water outlet is ideal. The best way
to select the location is to stand centrally in front of the outlet and extend
you right forearm in front of you in a natural arc. Be sure that passing
traffic cannot trigger the sensor. Allow at least 400mm clearance.
-
Ensure that when selecting a mounting position nothing is within range of
the sensor. If the sensor unit is installed into a location where a nearby
wall or object is reflecting the Infrared light back, the unit is effectively
blinded and will not operate. It is similar to having a torch shone into your
eyes.
Note: Outlets are not supplied and must be ordered separately.
COMPONENT DIMENSIONS
© Galvin Engineering Pty Ltd
Typical Installation
TZ-FLOWSENC24- STAINLESS STEEL FACE PLATE
WITH CONCEALED WALL SENSOR ASSEMBLY
Version 1.1, 30 April 2021, Page 3 of 11
Cut out details for Galvanised
box (not supplied as a
standard)
- If the unit is supplied with a
Galvanised Inwall electrical
box and stainless steel face
plate. Assembly should be
mounted flush to the wall over
a 98mm x 60mm cut-out.
Ensure wall depth is between
45mm minimum - 70mm
maximum from finished wall
surface to the back of box.
Do not install sensor
under the spout.