3. Testing
Once fitted, connect the water lines & turn on water.
Check for leaks and correct operation.
TROUBLESHOOTING
PROBLEM
Water is not flowing or
inconsistent flow.
Continous flow of
water.
Rate of flow
inadequate.
Button hard to activate.
Water shuts off upon
releasing the button.
CAUSE
Blocked flow restrictor / dirt in the
cartridge / water supply not on.
Top assembly cartridge loose or
internally obstructed or damaged.
The flow restrictor may not be
satisfactory due to inadequate supply
pressure.
Mains pressure may be too high.
Small spring at the bottom of the
cartridge piston dislodged.
th
Version 3,15
July 2020,
Page 3 of 4
RECTIFICATION
Remove flow regulator from outlet and
remove debris. Install an inline strainer to
stop further blockages. Ensure water
supply is turned on.
Remove cartridge, clean with water and re-
grease spindle if required.
Remove flow restrictor and replace with a
flow restrictor of different capacity to suit
(available from Galvin Engineering).
Reduce mains pressure to below 500kPa.
Relocate spring & regrease spindle if
required.