Installation & Operation Manual
INSTALLATION
Planning
This gas detection and ventilation control system is designed for installation into car parking
facilities and enclosed garages in the United States of America.
It is designed to be paired with AGS Nitrogen (NO
that will be linked via MODBUS back to this Parksafe control panel. The Parksafe control panel
will monitor the connected detectors in numbers up to 16 per panel.
The Parksafe will make or break a dry contact internally on Alarm 1 and a second contact on
Alarm 2. This is to have a live feed to the ventilation system wired through the contact so that on
alarm, the Parksafe can activate the fans. This can either be via a direct live to the fan or via a
run signal. There is a second relay for Alarm 2 that will activate after alarm 2 has been activated
for an extended period of time. This can be used for a link to the BMS or other external indication
device. The Parksafe also has the 0-10VDC output to allow the panel to drive VSD's based on
the gas detector outputs.
The Parksafe is designed to be located in an office or area within the carpark not accessible to
the public.
Please refer to your detector manual for important information regarding coverage, location
and positioning including areas and conditions to avoid.
Generally, the installation height of a sensor for Nitrogen Dioxide would be close to the ground,
and for Carbon monoxide gases, sensors would be positioned at a higher point in the area. Any
recommended heights may vary based on air flow and temperature conditions in addition to
the proposed application and location.
Carbon Monoxide (CO) gas
Nitrogen Dioxide (NO
Typical Installation Arrangement
Placing the Parksafe panel at eye level allows for optimum monitoring of the display screen.
AGS Parksafe - IOM Iss: DRAFT 3 06-20
Breathing Zone - 1700mm (5ft 6") from ground level.
) gas
Low Level - 300mm (1ft) from ground level.
2
) and Carbon Monoxide (CO) gas detectors
2
Parksafe Control Panel
3