Majestic VFR32C Kurulum ve Kullanım Talimatları Kılavuzu - Sayfa 8

Kapalı Şömine Majestic VFR32C için çevrimiçi göz atın veya pdf Kurulum ve Kullanım Talimatları Kılavuzu indirin. Majestic VFR32C 20 sayfaları. Vf, vfr series vent-free fireboxes

VF/VFR Vent-Free Fireboxes
Ensure that minimum clearances shown in Figures 4
through 8 are maintained. Left and right clearances are
determined when facing the front of the firebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
fire hazard.
1. Sidewall clearances: The clearance from the inside
of the appliance to any combustible wall should not be
less than 9". Figure 4
. Ceiling clearance: The ceiling must be at least 4"
from the top of the firebox opening. Figure 4
3. Back wall clearance: The appliance may be placed
against a combustible back wall.
FP687
Figure 4 -
Clearance and Height Requirements
FP2687
4. Mantel clearances: The canopy supplied with the unit
must be installed. If a combustible mantel is installed,

minimum clearances

it must meet the clearance requirements as shown in
Figure 5. However, if lower mantel height is desired,
refer to Page 14, Figure 6.
8
4 2
M i
"
n i m
u m
9 "
M i
n i m
u m
9 "
M i
n i m
u m
Combustible
Material Can
Contact Top
of Fireplace
FP690
Figure 5 -
Mantel Clearances
FP2690
1"
Mantel clearances
FP69
2 "
3"
Figure 5a -
Mantel Leg Clearance
FP2692
mantel leg clearance
FP691
Figure 6 -
Mantel Heights for Wide Profile Canopy
MINIMUM CLEARANCES
12"
10"
23"
8"
21"
6"
19"
2 "
16"
12"
Noncombustible Material
Only if Needed to Cover
Radiant Top Face
Finish Wall
Combustible
Material Area
"
"
"
6"
5"
7 "
45°
6"
7 "
9"
12"
8"
14"
8"
FP2691
mantel clear wide canopy
71D0531