WIRING SCHEMATIC
Assembly
The base of the detector can be mounted directly on false ceiling surfaces, or on electric connection boxes shaped
octagonally (75mm, 90mm or 100mm), round (75mm) or square (100mm), with no need for a mechanical adapter.
Wiring
Disconnect the supply voltage of the detection loop before installing the detector base.
§
Connect the positive input of the detection loop to the + terminal (positive input of the detection loop).
§
Connect the negative input of the detection loop to the - terminal (negative input of the detection loop)
¡
If a remote action indicator is to be installed, connect the positive of the indicator to the +C terminal or positive of
auxiliary supply and the negative to the R terminal.
AUXILIARY SUPPLY
INDICATOR
ALGORITHMIC LOOP
The action indicator can be fed from the detector itself, taking into account the total consumption of the loop, or by means
of an auxiliary supply.
If an auxiliary supply is used, the negative of the auxiliary supply should be joined to the negative of the algorithmic loop.
Ae-man-819-0.0 v1.1
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
.
INDICATOR
TECHNICAL MANUAL
Installing the detector
§
Position the detector on the base of the detector, aligning
the marks as indicated in the figure.
§
Rotate the detector gently clockwise until it is well coupled.
§
After installing all the detectors, reconnect loop supply
voltage.
PRECAUTIONS
§
To prevent contamination of the detector, and the resulting loss of guarantee, keep the protective cover in place
until the area where the detector has been installed is clean and dust-free.
§
The protective cover does not assure complete protection against all types of dust or penetration by foreign
substances, for which reason removal of the detector from the base is recommended if construction activities
(painting, sanding,...) are to be carried out, which can produce dust in suspension.
§
The detector should not be painted. The painting can block the air inlets to the optical chamber and alter its
operation and sensitivity.
§
The protective cover should be removed before starting up the system.
VERIFICATION OF OPERATION
The detectors must be tested after installation and undergo periodic maintenance.
Before carrying out the operating tests, notify to the competent authority that maintenance tasks are being carried out
in the fire detection system, and make sure that all the evacuation, operation and tripping functions for automatic
extinguishing are disabled.
§
When removing the detector from the base, the area should be put in the fault state. If this does not take place,
check the wiring of the detector base, and that it is correctly programmed in the Algorithmic Panel.
§
Check that the detector is working, by observing that it emits green colored flashes every 10 s, provided this
function has not been inhibited individually from the detector itself, or generally from the Algorithmic Fire
Detection Panel. If the flashing is not inhibited and the detector does not flash, this means it has failed or the
wiring is faulty.
§
Smoke test.
§
Activate the detector by applying detector test aerosol. When sufficient smoke has entered the chamber, the
detector will go to the alarm state and activate the red LED in fixed mode.
Heat test.
Apply a hot air blast at a temperature of between 65°C and 80°C at a distance of a few centimetres. The detector
should be activated in a time period of no more than 30 s, activating the red colored LED in a permanent mode.
§
If we have connected a remote action indicator, it will also light up. If it does not do so, check the wiring.
The detectors that have not passed the operating tests should be replaced and repaired.
When the tests have been completed, reconnect the evacuation, operation and extinguishing functions again, and
notify the competent authority that the fire detection system is again in service.
Ae-man-819-0.0 v1.1
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
SOCK ET
1º: ALINGN THE LED WIT H
THE M ARK O N T HE
2º: ROTATE THE DETE CTOR 30º
SOCKET AND I NSERT THE
30º
DETECTOR I N THE BASE.
LED
TECHNICAL MANUAL