AFRISO OSA 3 Manuel - Sayfa 8

Ölçüm Cihazları AFRISO OSA 3 için çevrimiçi göz atın veya pdf Manuel indirin. AFRISO OSA 3 20 sayfaları. Level alarm for oil separator

AFRISO OSA 3 Manuel

Installation

Wiring the system using multi-core cables
Note:
Read the installation instructions
!
Installation should only be carried
out by a suitably qualified Instal-
lation Engineer.
The intrinsically safe circuit must
not be earthed
When connecting more than 1 sensor it is
recommended that a junction box is used.
If a junction box is not used all cable joints
should be sealed using heat shrink tubing.
When connecting an ES8 sludge sensor an
external junction box should be used that
allows the shielded cable to be grounded
to earth.
When making connections between the
central control unit and a junction box this
should be interconnected using a multi-
core cable (6-core 1.0mm²) with connec-
tions made as shown in the following
diagram.
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • [email protected] • www.afriso.se
8
Seperator alarm OSA 3 • Manual
Terminals
K1: 230 VAC, 4 VA
K2: R1 Voltage free relay output (Symbols
on the circuit board are indicated in the
alarm condition)
K2: R2 Voltage free relay output (Symbols
on the circuit board are indicated in the
alarm condition)
K4: Terminal contact for membrane keypad
ribbon cable (not shown)
K3: 1-G Capacitive sensor ES4
K3: 2-G Thermal sensor R6-S
K3: 3-G Sludge sensor ES8
Recommended cable
Power supply: 3 x 1.5 mm²
Multi-core cable to junction box: 6 x 1 mm²
1 2 3 4 5 6
2
2
2
1
1
1
Shield
OSA 3