APPENDIX TO THE INSTRUCTION MANUAL OF 3-WAY MIXING VALVES ARV VARIO PROCLICK
AFRISO Sp. z o.o.
Szałsza, ul. Kościelna 7
42-677 Czekanów
www.afriso.pl
On each of the ARV Vario ProClick 3-way mixing valves there is a nameplate with three marked Kvs coefficent values.
In addition, it is also possible to select intermediate values between these values.
The diagrams below show a simplified way of selecting the Kvs value for each valve size. If the selected valve has
a pressure drop value of less than 3 kPa at the minimum Kvs value, select a valve with a smaller diameter and for
this determine the required Kvs. If the pressure drop value is bigger than 15 kPa at the maximum Kvs value, select
a valve with a larger diameter and for this determine the required Kvs.
The procedure for Kvs selection is described in detail in the valves manual in chapter:
setting".
DN20: ARV 362 VARIO PROCLICK, ARV 382 VARIO PROCLICK
Example:
1. Circuit power: 30 kW
2. Temperature diference: 15 K
3. Intersecaon point in the pressure drop range 3-15 kPa
4. Set 7 m³/h Kvs value on the valve
Customer Service Team
tel. 32 330 33 55
fax 32 330 33 51
3-way rotary mixing valves
ARV Vario ProClick
Art. Nr: 13 362 20, 13 382 20, 13 384 20,
13 385 20, 13 386 20, 13 387 20
"Valve selection and Kvs