ROOM THERMOSTATE
I.) ENTERING TO SERVICE MENU:
To Enter:
• Press UP and DOWN buttons simultaneously
• Enter service menu password by using UP and DOWN and press Mode/OK.
Note: The Service menu password is"58"
• Then go to Parameter you want to change by using UP and DOWN buttons then press
Mode/OK button
• Change the parameter by using UP and DOWN buttons then press Mode/OK button.
• Get out of menu by pressing ON/OFF button
Caution : All the changes on the service menu should be done
by authorized personnel. The damage and problems causing
by unauthorized changes on the service menu will be on user's
responsibility.
J.) SELECTING TEMPERATURE CONTROL POINT
There are 4 options that unit can check the temperature;
-Room thermostate
-Return Air
-Supply Air
-Outside Air
To select one of these;
• Press UP and DOWN buttons simultaneously
• Enter service menu password by using UP and DOWN and press Mode/OK.
Note: Service menu password is "58"
• Then go to Parameter ''118'' by using UP and DOWN buttons then press Mode/OK button
• Change the parameter by using UP and DOWN buttons then press Mode/OK button.
Parameter 118 could be one of below numbers
0-Room thermostate
1-Return Air
2-Supply Air
3-Outside Air
• Get out of menu by pressing ON/OFF button
Note: Selected sensor should be connected to the card . If not, there will be
"- -" symbol on the screen.
5
Control kit