GREEN BANK WG48200 Hızlı Başlangıç Kılavuzu - Sayfa 6

Kamera Aksesuarları GREEN BANK WG48200 için çevrimiçi göz atın veya pdf Hızlı Başlangıç Kılavuzu indirin. GREEN BANK WG48200 7 sayfaları. Lifepo4 battery system

LiFePO4 Battery System

4. OPERATION

Once the batteries are connected well, simply press On/Off button to enable the output of the battery pack.
48V Front view
4.1 Switch On / Off
1.Switch on: press On/Off button to switch on the battery, then the battery will do self-inspection before
enable output. The LED will show the SOC.
2.Switch off: press and hold On/Off button for 3 seconds, the battery will shut down directly.
Description for Communication port
Picture
PIN
1
2
3
4
5
6
7
8
DIP SWITCH
1-4
5

4.2 Description for LED

The SOC of the battery is shown by the LED
100%
75%
Note: The battery need to be fully charged for at least once in one month to ensure the accurate SOC
calculation.
Description
Trigger-GND
Trigger-VCC
NC
COMM-GND
RS485-B
RS485-A
CANL
CANH
Communication Address
Termination Resister
50%
25%
Flashing SOC<10%
08

4.3 ON / OFF or SOC Led (Mode or SOC)

ON/OFF
BATTERY MODE
GREEN LED
RED LED
LED1
POWER OFF
OFF
OFF
OFF
POWER ON
OFF
ON
ON
STANDBY
OFF
OFF
NORMAL
ON
OFF
DISCHARGE
ON
OFF
CHARGE
FLASH
OFF
LOW POWER
FLASH
OFF
ON
OFF
ON
OFF
ON
FAULT
OFF
ON
OFF
ON
OFF
ON
OFF
ON

4.4 DIP switch SW1-SW4 Description

DIP switch SW1-SW4 Description ①
Sw1 SW2 SW3 SW4
Remarks
0
0
0
0
means ID=0,communication address is0x00/0x10③
1
0
0
0
means ID=1,communication address is0x01④
0
1
0
0
means ID=2,communication address is0x02
1
1
0
0
means ID=3,communication address is0x03
0
0
1
0
means ID=4,communication address is0x04
1
0
1
0
means ID=5,communication address is0x05
0
1
1
0
means ID=6,communication address is0x06
1
1
1
0
means ID=7,communication address is0x07
0
0
0
1
means ID=8,communication address is0x08
1
0
0
1
means ID=9,communication address is0x09
0
1
0
1
means ID=10,communication address is0x0A
1
1
0
1
means ID=11,communication address is0x0B
0
0
1
1
means ID=12,communication address is0x0C
1
0
1
1
means ID=13,communication address is0x0D
0
1
1
1
means ID=14,communication address is0x0E
1
1
1
1
means ID=15,communication address is0x0F
Remark①: 1 in SW1-SW5 indicates ON status, and 0 indicates OFF status.
Remark②: When multiple battery packs communicate, the last battery pack SW5 needs to be in the ON
status, otherwise the communication may have interference.
Remark③: When the battery pack ID is set to 0, it means stand-alone operation, and it is not necessary to
detect whether the parallel condition is satisfied ⑤
Remark④: When the battery pack ID is set to 1-15, it means that the parallel operation is required, and it is
necessary to detect whether the parallel condition is satisfied ⑤
Remark⑤: The parallel condition is that the difference between the battery voltage of the local battery and
all the battery pack voltages is <3V, otherwise wait until the condition is satisfied
LiFePO4 Battery System
SOC
REMARK
LED2
LED3
LED4
OFF
OFF
OFF
ON
ON
ON
SOC
SOC<10%(DEFAULT ): LED1 FLASH
RUNNING/SOC
SOC<10%(DEFAULT ): LED1 FLASH
SOC
SOC<10%(DEFAULT ): LED1 FLASH
RUNNING
OFF
OFF
OFF
OFF
BATTERY VOLTAGE HIGH
ON
OFF
OFF
BATTERY VOLTAGE LOW
ON
OFF
OFF
CELL VOLTAGE HIGH
OFF
ON
OFF
CELL VOLTAGE LOW
OFF
ON
OFF
CHARGING CURRENT HIGH
ON
ON
OFF
DISCHARGING CURRENT HIGH
ON
ON
OFF
BMS TEMPERATURE HIGH
OFF
OFF
ON
BMS TEMPERATURE LOW
OFF
OFF
ON
CELL TEMPERATURE HIGH
ON
OFF
ON
CELL TEMPERATURE LOW
ON
OFF
ON
CURRENT SENSOR ABNOMAL
DIP switch SW5 Description②
Remarks
SW5
means connect
1
120Ω resistor
means disconnect
0
120Ω resistor
09