This instrument may only be used within the ranges specified and
within low voltage systems up to 1000V.
Prior to usage ensure perfect instrument function (e.g. on known
voltage source).
The voltage detector is not to be used, if the battery cover is open.
The voltage detectors have to be kept dry and clean.
The voltage testers may no longer be used if one or several functions
fail or if no functionality is indicated.
Do not use this instrument under damp conditions.
Accurate measurements within a temperature range of -10°C up to
55°C, at relative humidity question <85%.
If the operator's safety cannot be guaranteed, the instrument must be
removed from service and sent in for repair.

1.4. Safety Precautions before use

• Meter shows obvious damage.
• Test Leads are damaged or insulation is open.
• Measurements are not correct.
All relevant statutory regulations must be adhered to when using this
instrument.

1.5. Safety Advices

• Depending on the internal impedance of the voltage detector and
presence of interference voltage there could be a different capability
of indicating the presence or absence of operating voltage.
• A voltage detector of relatively low internal impedance, compared to
the reference value of 100kΩ, will not indicate all interference
voltages having an original voltage value above the ELV level; When
in contact with the parts to be tested, the voltage detector may
temporarily discharge the interference voltage to a level below the
ELV, but it will return to the original value when the voltage detector
is removed.
• When the indication "Voltage Present" does not appear, it is highly
recommended installing earthing equipment before proceeding with
testing and maintenance.
• A voltage detector of relatively high internal impedance, compared to
the reference value of 100kΩ, may not clearly indicate the absence of
operating voltage in the presence of interference voltage.
5