Fujitsu UTY-XDZX Kurulum Kılavuzu - Sayfa 2
Klima Fujitsu UTY-XDZX için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. Fujitsu UTY-XDZX 8 sayfaları.
Make sure to operate through the any control unit. When the breaker is designed, locate it at a place where the users
cannot start and stop in the daily work.
CAUTION
Read carefully all security information before use or install this product.
The installation must be carried out in compliance with regulations in force in the place of installation and the installation
instructions of the manufacturer. This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
The units are not explosion proof and therefore should not be installed in explosive atmosphere.
Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between
contacts of 3mm for this unit.
The unit must be correctly earthed (grounded) and the supply line must be equipped with a differential breaker to protect
the persons.
Never touch electrical components immediately after the power supply has been turned off. Electric shock may occur.
After turning off the power, always wait 5 minutes before touching electrical components. If it caused the problem and
error, turn off the power supply immediately and never use it.
This unit contains no user-serviceable parts. Always consult authorized service personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation of the unit.
_2. About this
product_
The module has optional cloud connectivity for remote control and diagnostics. For setup of cloud connection go to
https://ecosmart.cloud
2.1 Precaution for using this product
When operating the unit from other source than IO a new command must be received by the device every 5 min to keep
the unit operating. If no command is received within timeout the unit will stop.
2.2 Package Content
UTY-XDZX Module
This installation manual
2.3 Field supplied material (This is mandatory.)
NTC Temperature sensor type: 10KOhm +/-1% @ 25-degree C - characteristics 3950K
(Recommend wire length is 2m. If you extend more wire length, please select the proper wire type, shielded wire
with proper decoupling of shielding is recommended, and ground current loops should be avoided.)
_3. Product
selection_
Please be sure to follow the technical manual concerning selection of outdoor unit.
※Regarding pipe size, pipe length and so on, please follow technical manual of product and manuals of outdoor unit.
3.1 Product lineup
Model name: UTY-XDZX
_4. Installation
work_
4.1 Selecting an installation location
Select installation locations that can properly fix this product. Select a location where there is no water intrusion, such as
along the wire, rain water and so on. Install the units securely so that they do not topple or fall. Please select the
installation location that a person except installation worker and service personal don't touch this product.
Install this product in a location which can withstand a load of at least 3 times the weight of the main unit and which will
not amplify sound or vibration. If the installation location is not strong enough, this product may fall and cause injuries.
This mark indicates procedures which, if improperly performed, might possibly result in
personal harm to the user, or damage to property.
and follow the instructions there.
WARNING
Page 2 of 8