Original Issue Date: 12/13
Model: 5/7.5/10EKD and 4/6/8EFKD
Market: Marine
Subject: Seawater Flow Switch Kit GM90489

Introduction

Installation of this kit involves adding a seawater flow
switch and replacing/relocating the seawater pressure
switch with a new switch that provides enhanced
protection for loss or low seawater flow.

Required Tools

The following tools and supplies are needed:
Electrical tape
D
Teflon tape
D
Loctite
R
565 general purpose pipe sealant paste
D
Drill and 3/16 in. drill bit
D
5/16 in. socket, 1/4 in. drive
D
10 mm socket, 1/4 in. drive
D
15 mm open end wrench
D
13 mm open end wrench
D
3/8 in. open end wrench
D
7/16 in. open end wrench
D
3 in. Phillips screwdriver
D
1/4 in. socket
D
1/4 in. drive ratchet
D
Hose cutter knife
D
Wire cutter
D
Rags
D

Safety Precautions

Observe the following safety precautions while
performing this procedure.
WARNING

Accidental starting.

Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
INSTALLATION INSTRUCTIONS
the
generator
set.
Disabling the generator set.
cause severe injury or death.
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Testing live electrical circuits.
current can cause severe injury or death. Have trained and
qualified personnel take diagnostic measurements of live
circuits. Use adequately rated test equipment with electrically
insulated probes and follow the instructions of the test
equipment manufacturer when performing voltage tests.
Observe the following precautions when performing voltage
tests: (1) Remove all jewelry. (2) Stand on a dry, approved
electrically insulated mat. (3) Do not touch the enclosure or
components inside the enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)
TT-1617 12/13
Accidental starting can
Before working on the
Moving parts.
Hazardous voltage or