Kohler 12RESM1 Kurulum Kılavuzu

2.1 General

Have an authorized distributor/dealer install the
generator set outdoors according to the instructions in
this manual. The generator set installation must comply
with the National Electrical Code (NEC) and local code
requirements. Do not install this generator set indoors.
Use the specifications provided here only in the initial
planning. Use the generator set and transfer switch
spec sheets, dimension drawings, and wiring diagrams
for installation.

2.2 Lifting

WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
The generator set weighs approximately 180 kg
(400 lb.). Use lifting bars inserted through the holes in
the skid to lift the unit. See Figure 2-1 for lifting hole
locations.
TP-6397 4/07

Section 2 Installation

2.3 Generator Set Inspection

Complete a thorough inspection of the generator set.
Check for the following:
D
Inspect the generator set for loose or damaged parts
or wires. Repair or tighten any loose parts before
installation.
D
Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil.
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher. See TP-6398, Operation
Manual, for additional information.

2.4 Location and Mounting

See Figure 2-1 for the generator set dimensions and
fuel and electric inlet locations. The drawing dimensions
are shown in millimeters, with inches in brackets. The
wiring kit is shown as packaged for shipping.
Locate the generator set outdoors. See Figure 2-2 for
the minimum clearance around the generator set.
Select a location where the generator set exhaust does
not blow on plants or other combustible materials. Do
not install the generator set where exhaust gas could
accumulate and seep inside or be drawn into a
potentially occupied building.
2.4.1

Standard Mounting

The generator set is shipped on a plastic mounting pad.
Prepare a flat, level mounting area covered with a weed
barrier and gravel as shown in Figure 2-2. Set the
plastic mounting pad directly on the gravel. Do not
install the mounting pad directly on grass.
2.4.2

High-Wind Enclosure Mounting

See Figure 2-3 for mounting details for the optional
high-wind enclosure.
Use
Section 2 Installation
13