1.12 Prestart Installation Check
Review the entire installation section. Inspect all wiring
and connections to verify that the generator set is ready
for operation. Check all items in the following Prestart
Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is
installed to prevent unfiltered air from entering the
engine. See the generator set operation manual for
instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Enclosure.
Check that all enclosure panels and
internal baffling are in place.
Exhaust System.
Check for exhaust leaks and
blockages. Check the muffler condition.
D
Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system
connections.
D
Check for corroded or broken metal parts and replace
them as needed.
D
Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
30
Section 1 Installation
1.13 Set Exerciser
Set the exerciser to automatically run the generator set
on the desired day and time every week. See TP-6734,
Operation Manual, for detailed descriptions of the
unloaded and loaded exercise operation.
Procedure to Set the Exerciser
1. Press the AUTO button on the controller.
2. Press the down arrow button (RDC) or the exercise
button (DC) to start an unloaded exercise. The
engine starts and runs a 20-minute unloaded
variable-speed exercise with system diagnostics.
EnLd is displayed.
3. If the generator set is connected to a Kohlerr Model
RRT transfer switch, the exercise can be changed
to a loaded exercise by pressing the down arrow
button (RDC) or the exercise button (DC) again
after the engine has started. E Ld is displayed.
4. After 20 minutes, verify that the exercise ends and
the engine shuts down automatically.
loaded exercise, the engine runs for 5 minutes or
until cool, and then shuts down.
The exercise will run every seven days at the same time
that the exercise was started.
Other transfer switches: For a loaded exercise with a
transfer switch other than a Kohlerr Model RRT, refer to
the transfer switch operation manual for instructions.
After a
TP-6733 8/11