Kohler 30RES Manuel - Sayfa 28

Taşınabilir Jeneratör Kohler 30RES için çevrimiçi göz atın veya pdf Manuel indirin. Kohler 30RES 36 sayfaları. Residential generator sets

Kohler 30RES Manuel

3.11 Belt Check

Check the belt tension at the intervals specified in the
service schedule. If the tension is not within
specification, adjust as necessary using the following
procedure. See Figure 3-12.
Adjust the tension of the alternator/fan belt so that the
belt can be depressed about 12.7 mm (0.5 in.) when
applying finger pressure. Use the following procedure
to adjust the belt.
2
1
4
3
1. Battery charging alternator pulley
2. Adjusting screw
3. Check the alternator belt tension here
4. Alternator pivot screw
Figure 3-12 Belt Tension
Belt Tensioning Procedure
1. Disconnect the battery, negative lead first.
2. Loosen the pivot and adjusting screws.
3. While prying the battery charging alternator
outward, tighten the adjusting screw.
4. Tighten the pivot screw.
5. Recheck and adjust as necessary.
6. Reconnect the battery, negative lead last.
Note: Also check the fan belt for cracks or tears
and replace the belt if necessary.
28
Section 3 Scheduled Maintenance

3.12 Storage Procedure

Follow the procedure below when storing your
generator set for a long period (3 months or more).
1. Start and run the generator set until it reaches
operating temperature or about 15 minutes.
2. Stop the generator set.
3. Change the oil and oil filter; see Section 3.4.5, Oil
and Filter Change.
4. Drain the fuel completely from the fuel tank to
prevent accumulated moisture from mixing with the
fuel.
5. Check the engine coolant protection; see
Section 3.8.
Note: Use antifreeze capable of withstanding the
lowest possible temperatures.
6. Keep spark plugs in their holes or seal spark plug
holes with suitable threaded metal plugs.
7. Clean the exterior of the generator set and spread a
light film of oil or silicon spray over any exposed
surfaces that may be subject to rust or corrosion.
8. Seal the air inlet, exhaust pipe, and fuel tank cap
with tape.
9. Disconnect and remove the battery. Place the
battery in a warm, dry location for the storage
period. Recharge the battery once a month to
maintain a full charge.
10. Select a well-ventilated (not humid or dusty)
location to store the generator.
11. Cover the entire unit with a dust cover.
Note: Run the generator set once a month
whenever possible.
TP-6344 4/09