operation manual
MPPT solar charge controller X45/10
8.3 Under Voltage Lockout (LVD)
To prevent deep discharge of the load, the controller turns off the load as soon as the battery voltage
falls below the LVD voltage. Should this happen, the battery must be fully charged before using it
again.
1. Lithium batteries: LVD=9.0-15.0V (default: 9.0V)
2. Gel, wet and AGM batteries:
The low voltage protection of the controller can be divided into two types: a. Battery voltage control:
Low voltage cut-off adjustment range: 10.8-11.8V (default: 11.2V) b. Battery capacity control:
Setting range of undervoltage shutdown: SoC 1 – SoC 5
8.4 Low Voltage Reclosing (LVR)
If the undervoltage lockout is triggered, the controller will not reestablish the charge
connection until the battery voltage is above the LVR voltage.
1. Lithium batteries: LVR= 9.6 to 16.0 V 2.
Gel, wet and AGM batteries: LVR= 11.4 to 12.8 V
The LVR should be higher than the LVD.
The LVD should be at least 0.6V.
If you want to change the LVD, you must first change the LVR.
Page 10
SoC
SoC 1
SoC 2
SoC 3
SoC 4
SoC 5
status
11.0 - 11.6V
11.1-11.7V
11.2 - 11.8V
11.4-11.9V
11.6 - 12.0V