Technical Bulletin
Replacement of the electric actuator (illustration 2)
Replacement due to 5 years mantenance the electric actuator
must be replaced with a new one as described above:
a) unscrew the actuator (1);
b) disconnett
c) screw the new actuator checking that the part outside
measure will be 2 mm.
Replacement due to the explosion of the pyrotechnical change:
a) unscrew the actuator (1);
b) unscrew the valve from the cylinder;
c) extract the piston (2) and replace the O-ring (3);
d) after having put the piston in the valve, screw the valve on
the cylinder;
e) put the new bulb (4) in the valve;
f ) pull outside the nut (5) and turn the leverage (6) till it is
positioned on the bulb. Release the nut (5) (be sure that
the
leverage (6) is locked) replace the cartridge with a new
one
and screw it till the outside part will be between 2 mm.
Use Remarks
1) the extinguisher can be used on electric fires
(control panel or switch boards).
2) ventilate room after gas discharge / intervention.
3) refill and recharge the unit even partially used.
A
2
3
PHASE
EVENT
TRANSPORT AND
INSTALLATION
OPERATION
OVER-PRESSURE
WEAR/CORROSION
MAINTENANCE
IMPROPER
DEPRESSURIZATION
Lombardia Street 310, 20861 S.Dam. Brugherio
Tel. +39 - 039 - 839631 - Fax. +39 - 039 - 8396349
1370
e-mail:[email protected]
6
5
4
7
1
illustration 2
INSTRUCTIONS FOR THE USER
DANGER
FALL
BUMP
BURSTING/
REDUCING OF
THE THICKNESS
VIOLENT CAST OF
COMPONENT OR
PART OF THEM
Technical data are subject to modification
for improvements without prior notice
a.b.s. S.r.l. (Milan) Italy
www.absfire.it
Capital euro 2,000,000.00
Maintenance and disposal:
Maintenance, handling, storage and disposal of the unit must be
done following local regulations. A company who makes above
activities and disposal of extinguisher agent should be authorized
for such works.
Periodically check that pressure gauge indicators is on the green
field, that means extinguisher is still well pressurized and ready to
be used.
If pressure gauge indicator is on red field, refer to authorized
maintenance company.
Periodic inspection, servicing and tests:
The maintenance of unit should be done at least every 6 months,
or according to local law.
Hydraulic tests of extinguisher body must be done every 12 years.
PRESSURE SWITCH (cod. 23024) PRESET AT 5 bar
Low pressure switch cod. 23024, which directly indicates alarm
leaks or discharging.
Code 23024
Attention (detail "A"):
During the maintenance of the valve
check as well that the piston is passing
the body valve as detail "A"
SUGGESTIONS AND
PRECAUTIONS
Carry in container which protects the
product from bump.
Pressurize extinguishers at 14 bar at
20°C. The pressurization must be
done by means of a well-tuned
pressure reducer.
Avoid:
- Bump which can damage
the painting.
- Washing and contact
with corrosive materials.
The maintenance must be done by
qualified company (in extinguishers
maintenance).
The disposal must be done by qualified
company (in chemical products
disposal).
Detail "A"
MEASURES
In case of dent, give the product back to
the maker for control.
If corrosion is pointed out please call
the maintenance company for an
immediate hydraulic test.
The maintenance of the extinguisher
must be done according to the local
regulation.
The disposal must be done by
qualified and authorized company only who
make it according to the local regulations
In case of contact with POWDER, wash
immediately with a large amount of water.