DeZURIK
3650-7200 PEC Eccentric Valves
Removing Valve from Pipeline
To remove the entire valve assembly from the pipeline, follow these steps.
This valve is a pressure vessel. Failure to release pipeline pressure may result in
personal injury and/or flow system damage. Completely release pipeline pressure
before removing the actuator from the valve or removing the valve from the pipeline.
1. Relieve pipeline pressure and drain portion of system where valve is located.
2. Close the valve.
Moving parts from accidental operation of power actuator can cause personal injury
or equipment damage. Disconnect and lock out power to actuator before servicing.
3. If the actuator is powered, disconnect and lock out the pneumatic, hydraulic, or electrical power
to prevent accidental operation of the actuator.
4. Support the valve assembly, then remove the flange bolts.
5. Remove the valve from the pipeline.
Field Test
Stroke the valve between the fully open and fully closed positions to verify that the valve and actuator
are functioning properly.
Emergency Operation
Operate the valve as under normal conditions, taking care to bring the plug to the position required by
the particular emergency condition.
Predicted Wear of Parts
Length of service for parts subject to wear is dependent on service conditions.
D10019