Slab Mounting
Discharge Air
Building
Structure
Unit must be grounded in accordance with national and local
codes. Failure to ground unit properly can result in personal
injury or death.
Refer to the furnace or blower coil Installation Instructions
for additional wiring application diagrams and refer to unit
rating plate for minimum circuit ampacity and maximum
overcurrent protection size.
1. Install line voltage power supply to unit from a properly
sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the low
voltage field wiring.
2. Ground unit at unit disconnect switch or to an earth
ground. To facilitate conduit, a hole is in the bottom of the
control box. Connect conduit to the control box using a
proper conduit fitting. Units are approved for use only
with copper conductors. 24V Class II circuit connections
are made to the low voltage pigtails. A complete unit wiring
diagram is located inside the unit control box cover (see
also page 18 of this instruction).
3. Install room thermostat on an inside wall that is not subject
to drafts, direct sunshine, or other heat sources.
4. Install low voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit (see Figure 3).
5. Do not bundle any excess 24V control wire inside control
box. Run control wire through installed wire tie and tighten
wire tie to provide low voltage strain relief and to maintain
separation of field-installed low and high voltage circuits.
506251-01
Mounting Slab
Ground Level
Figure 2
WARNING
Thermostat Designations
Thermostat
R
W1
Cooling
Y
Indoor Blower
G
C
See unit wiring diagram for power supply connections.
If the indoor unit is not equipped with a blower relay, one must be
field supplied and installed.
Do not connect C (common) connection between indoor unit and
thermostat except when required by the indoor thermostat. Refer
to thermostat installation instructions. C (common) connection
between indoor unit and outdoor unit required for proper
operation.
Refrigerant Piping
Refrigerant can be harmful if inhaled. Refrigerant must
always be used and recovered responsibly. Incorrect or
irresponsible use of refrigerant can result in personal injury
or death.
If the 4SCU14LE unit is being installed with a new indoor
coil and line set, the refrigerant connections should be made
as outlined in this section. If an existing line set and/or indoor
coil will be used to complete the system, refer to this section
as well as the section that follows entitled Flushing Existing
Line Set and Indoor Coil.
If this unit is being matched with an approved line set or indoor
coil which was previously charged with R22 refrigerant, the
line set and coil must be flushed prior to installation. If the unit
is being used with an existing indoor coil which was equipped
with a liquid line which served as a metering device (RFCI),
the liquid line must be replaced prior to the installation of the
4SCU14LE unit.
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections).
Select line set diameters from Table 2 on page 4 to ensure
that oil returns to the compressor. Size vertical suction riser
Issue 1015
Indoor Unit
Power
Outdoor
R
Unit
Heat
W
Y
G
C
Figure 3
WARNING
Y1 Outdoor Unit
C Outdoor Unit