Technical specifications
Table 26 Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Table 27 Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
Note:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
R740xd Owner's Guide
32
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.
Note:
This condition applies to data center environments only. Air
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
Note:
Air entering the data center must have the MERV11 or MERV13
filtration.
Air must be free of conductive dust, zinc whiskers, or other conductive
particles.
Note:
This condition applies to data center and non-data center
environments.
Air must be free of corrosive dust.
l
Residual dust present in the air must have a deliquescent point less
l
than 60% relative humidity.
Note:
This condition applies to data center and non-data center
environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.