The S6100–ON is suitable for installation as part of a common bond network (CBN).
You can install the system in:
● Network telecommunication facilities
● Data centers
● Other locations where the National Electric Code (NEC) applies
For more information about S6100–ON specifications, see Specifications.
NOTE:
Install the S6100–ON system into a rack before installing any optional components.
Topics:
•
Site selection
•
Cabinet placement
•
Rack mounting
•
System ground
•
Fans and airflow
•
Power
•
Storing components
Site selection
Install Dell equipment in restricted access areas.
A restricted access area is one in which service personnel can only gain access using a special tool, lock, key or other means of
security. Access is controlled by the authority responsible for the location.
Ensure that the area where you install your S6100–ON system meets the following safety requirements:
● Near an adequate power source. Connect the system to the appropriate branch circuit protection as defined by your local
electrical codes.
● Environmental temperature range is from 32° to 113°F (from 0° to 45°C).
● The switch operating ambient temperature range is from 10° to 35°C (from 50° to 95°F).
● Relative humidity is from 5 to 85 percent noncondensing.
● In a dry, clean, well-ventilated and temperature-controlled room, away from heat sources such as hot air vents or direct
sunlight.
● Away from sources of severe electromagnetic noise.
● Positioned in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for proper ventilation and
access.
Cabinet placement
Install the S6100–ON only in indoor cabinets designed for use in a controlled environment.
Do not install the S6100–ON in outside cabinets. For cabinet placement requirements, see
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.
12
Site preparations
Site preparations
Site
selection.